Operation Manual
MI 3309 BT DeltaGT Autotest sequences
67
Figure 6.37: Substitute leakage - P starting screen
After the measurement is carried out the Substitute leakage - P result screen is displayed.
Figure 6.38: Substitute leakage - P result screen
Options in Substitute leakage - P result screen:
NEXT
Proceeds with the next measurement.
REPEAT
Repeats the test (use in case of multiple isolated / SELV / PELV
accessible points). Highest result will be stored.
6.5.8 Touch Leakage measurement
The test is offered if it is applicable according to the autotest setting. The Touch leakage -
starting screen is displayed first. Measurement and options in Touch leakage screen are
described in chapter 5.2.9 Touch leakage.
Figure 6.39: Touch leakage starting screen
After the measurement is carried out the Touch leakage result screen is displayed.
Figure 6.40: Touch leakage result screen
Options in Touch leakage result screen:
NEXT
Proceeds with the next measurement.
REPEAT
Repeats the test (use in case of multiple isolated / SELV / PELV
accessible points). Highest result will be stored.
6.5.9 (P)RCD test
The test is offered if it is applicable according to the autotest setting. The (P)RCD test
starting screen is displayed first.
Measurement and options in (P)RCD test starting screen are described in chapter 5.2.10
RCD test.