MI 3309 BT DeltaGT Appendix B – Pre-programmed autotests (GER)
84
Appendix B – Pre-programmed autotests (GER)
Pre-programmed autotest sequences table
Autotest shortcut code
A01 A02 A03 A04
Kl_1_Iso Kl_1_Iso_BLT Kl_1_Ia Kl_1_Ia_BLT
Visual test
Earth
continuity
Output 200 mA 200 mA 200 mA 200 mA
Limit
0.30 0.30 0.30 0.30
Time 5 s 5 s 5 s 5 s
Insulation
Output 500 V 500 V
Limit
1.00 M 1.00 M
Time 5 s 5 s
Insulation
(probe)
Output
500 V
Limit
2.00 M
Time
5 s
Sub. leakage
Output 40 V 40 V
Limit 3.50 mA 3.50 mA
Time 5 s 5 s
Sub. leakage
(probe)
Output
40 V
Limit
0.50 mA
Time
5 s
Differential
leakage
Output
230 V 230 V
Limit
3.50 mA 3.50 mA
Time
180 s 180 s
Touch
leakage
Output
230 V
Limit
0.50 mA
Time
180 s
Functional test
Power*
Output 230 V 230 V 230 V 230 V
Limit
Time 180 s 180 s 180 s 180 s
TRMS clamp
current
Output
Limit
Time
Polarity test
* optional