MI 3309 BT DeltaGT Appendix D – Pre-programmed autotests (NL)
91
Pre-programmed autotest sequences table (cont’d)
Autotest shortcut
code
05 06 07 08
KL_3_ALG KL_1_AGMD KABEL_5M_2.5MM KABEL_15M_2.5MM
Visual test
Earth
continuity
Output
200 mA 200 mA 200 mA
Limit
0.30 0.30 0.50
Time
5 s 5 s 5 s
Insulation
Output
500 V 500 V 500 V
Limit
1.00 M 1.00 M 1.00 M
Time
5 s 5 s 5 s
Insulation
(probe)
Output 500 V 500 V
Limit
0.50 M 2.00 M
Time 5 s 5 s
Sub. leakage
Output
Limit
Time
Sub. leakage
(probe)
Output
Limit
Time
Differential
leakage
Output
230 V
Limit
1.00 mA
Time
5 s
Touch
leakage
Output
230 V
Limit
0.50 mA
Time
5 s
Functional test
Power*
Output
Limit
Time
TRMS clamp
current
Output
Limit
Time
Polarity test
* optional