Operation Manual
MI 3309 DeltaPAT Technical specifications
21
Test current..................... ½I
N
, I
N
, 5I
N
(I
N
= 10 mA, 15 mA, 30 mA)
Start angle ...................... 0, 180, both
Test modes ..................... single, autotest
Test terminals MAINS terminal
Specified accuracy is valid for complete operating range.
3.7.2 Portable RCD trip-out time
Range Resolution Accuracy
0 ms 300 ms(½I
N
)
0.1 ms
0 ms 300 ms (I
N
)
0.1 ms
3 ms
0 ms 40 ms (5I
N
)
0.1 ms
1 ms
Powered by..................... mains
Test current..................... ½I
N
, I
N
, 5I
N
(I
N
= 10 mA, 15 mA, 30 mA)
Start angle ...................... 0, 180, both
Test modes ..................... single, autotest
Test terminals Test socket – IEC test terminal
Specified accuracy is valid for complete operating range.
3.8 Power
Apparent power
Range Resolution Accuracy
0.00 kVA 4.00 kVA
0.01 kVA
(5 % of reading + 3 digits)
Powered by..................... mains
Test duration:.................. 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Test terminals ................. MAINS terminal
* Measurement is limited to 120 s if (I
load
> 10 A).
3.9 TRMS Voltage
Range Resolution Accuracy
80 300 V
1 V
(2 % of reading + 2 digits)
Result type................................ True r.m.s.
Nominal frequency range.......... 0 Hz, 50 Hz 60 Hz
Frequency accuracy ................. Indication only
Test terminals ........................... MAINS terminal