Operation Manual

MI 3309 DeltaPAT Single test
46
a) Testing of standard RCD
b) Testing of PRCD via mains socket
c) Testing of PRCD via test socket
Figure 5.36: Testing of RCD and PRCD
5.2.10.1 (P)RCD single test
In single test a fast (P)RCD test with selected test current and with one or both starting
polarities is performed.
Trip-out time measurement procedure
Measuring PRCD
Select the RCD test function.
Select test mode.
Set test parameters.
Connect tested PRCD / device to an external voltage socket. Connect the IEC cord
to the instrument’s MAINS terminal and PRCD (see figure 5.36b).
Depending on the type of PRCD, it may be necessary to manually switch it on.
Press the TEST key to perform measurement.