Operation Manual
MI 3309 DeltaGT Appendix C – Pre-programmed autotests (UK)
76
12 m 0.30 Ω 25 A 0.75 mA PRCD: 30 mA
Auto
active 297
1.5mm
2
/ 15 A
<=5 m 0.20 Ω 25 A 0.75 mA PRCD: 30 mA
Auto
active 303
7.5 m 0.20 25 A 0.75 mA PRCD: 30 mA
Auto
active 304
10 m 0.20 25 A 0.75 mA PRCD: 30 mA
Auto
active 305
12 m 0.30 25 A 0.75 mA PRCD: 30 mA
Auto
active 306
15 m 0.30 Ω 25 A 0.75 mA PRCD: 30 mA
Auto
active 307
UNKNOWN
<=5 m 0.20 Ω 25 A 0.75 mA PRCD: 30 mA
Auto
active 312
7.5 m 0.20 25 A 0.75 mA PRCD: 30 mA
Auto
active 313
10 m 0.20 25 A 0.75 mA PRCD: 30 mA
Auto
active 314
12 m 0.30 25 A 0.75 mA PRCD: 30 mA
Auto
active 315
15 m 0.30 Ω 25 A 0.75 mA PRCD: 30 mA
Auto
active 316
20 m 0.40 25 A 0.75 mA PRCD: 30 mA
Auto
active 317
30 m 0.50 25 A 0.75 mA PRCD: 30 mA
Auto
active 318
40 m 0.60 25 A 0.75 mA PRCD: 30 mA
Auto
active 319
50 m 0.80 25 A 0.75 mA PRCD: 30 mA
Auto
active 320
Type Portable RCD
Earth Bond
Limit Out
Leakage
Limit
RCD Polarity Code
0.10 25 A 0.75 mA PRCD: 30mA
Auto
active 400
Type Class III equipment
Visual Code
500
Meaning of symbols used in autotest shortcut codes tables:
test/measurement enabled
- test/measurement disabled