Operation Manual
MI 3310 / MI 3310A SigmaGT Working with results
113
7.4.1 Send to serial printer
..............................
METREL
Testing laboratory
Horjul, Slovenia
..............................
DEVICE 11072010
TEST SITE METREL
LOCATION OFFICE 1
TIME/DATE 09:31 11-JUL-2008
USER TOMAZ
RESULT: PASS
----------------------------------------
VISUAL PASS
EARTH BOND It: 10A~ Rlim: 0.10 Ohm
1. R = 0.03 Ohm PASS
INSULATION Ut: 500V Rlim: 1.00 MOhm
1. R = 178.9 MOhm PASS
LEAKAGE Ut: 230V~ Ilim: 0.75 mA
1. I = 0.23 mA PASS
POWER
1. P = 2.01KVA PASS
DEVICE NAME: APP 1
RETEST PERIOD : 11/07/2009
REPAIRING CODE: 021268505
COMMENTS: -
========================================
END OF DATA
An example of data sent to serial printer
Notes:
When working with serial printers, the baud rate is set by default to 9600 bps.
Software transfer control uses XON (CTRL-Q) and XOFF (CTRL-S) characters.
Hardware transfer control uses DTR line.
7.4.1 Send to barcode / QR code printer
Refer to chapter 4.2.8.6 Instrument settings and Appendix B for detailed information
about barcode systems used when printing barcode or QR-code labels.