Operation Manual
MI 3310 / MI 3310A SigmaGT Measurements
51
Test circuits for Insulation - S resistance measurement
Measurement of insulation resistance of class II DUT
Measurement of insulation resistance of accessible isolated conductive parts of fixed
installed DUTs
Insulation resistance – S probe measurement procedure
Select the Insulation resistance-S probe function.
Set test parameters.
Connect device under test to the instrument (see figures above).
Connect EB/S probe to accessible conductive parts of the DUT.
For fixed equipment:
Disconnect mains supply of the fixed equipment;
Connect LN test socket of the instrument to L/N terminals of the fixed equipment;
Connect EB/S probe to accessible conductive parts of the fixed installed DUT
Press the START key for measurement.