Operation Manual

MI 3310 / MI 3310A SigmaGT Autotest sequences
99
ENTER
Proceeds to the next autotest sequence measurement (in continuous
measurement mode only).
REPEAT (F3) Repeats the TRMS current measurement.
SKIP (F4) Skips TRMS current measurement.
6.5.11 RCD/PRCD test
Measurement is described in chapter 5.2.10 RCD/PRCD test.
If the RCD test fails or was skipped other tests will not be carried out because of safety.
RCD test menu
Keys:
START
Starts the RCD test.
Proceeds to the next autotest sequence measurement.
REPEAT (F3) Repeats the RCD test.
SKIP (F4) Skips the RCD test.
6.5.12 Functional test
The main objective of this test is to verify correct operation of the DUT.
Especially items relevant for safety should be checked:
- All main operating modes. Testing power during this check is useful.
- Mechanical operation (motors, rotating parts)
- Safety relevant functions (alarms, switches etc)
A PASS/ FAIL ticker can be committed manually.
The power measurement can be carried out optionally and is stored too. The Power
measurement is described in chapter 5.2.11 Functional test.
Functional test menu