Operation Manual
MI 3310 / MI 3310A SigmaGT Appendix C – Country notes
131
Heating elements L: >0.5 MΩ - Classify the iron as a standard DUT.
8
Insulation test
Accessible cond. Parts L: >2.0 M
Information that insulation resistance
measurement of Class 2 parts will be
included in the (NEN / Class I / with isolated
accessible conductive parts) test procedure.
9
Leakage test method:
Leakage
Selection of leakage current test method:
- Select substitute leakage measurement.
10
Limit / Device type
General device I < 1 mA
Classify the iron as an standard DUT with
power <3.5 kW.
11
Touch leakage method: Substitute
leakage
Limit < 0.5 mA
Information that substitute leakage current
measurement class 2 parts will be included
in the (NEN / Class I / with isolated
accessible conductive parts) test procedure.
The following parameters can be viewed in general for all measurements / tests:
Measurement mode,
Output test voltage or current (except in visual test and TRMS current
measurement),
Pass level (except in visual test),
Measurement duration (except in visual test).