Operation Manual
MI 3310 / MI 3310A SigmaGT Appendix C – Country notes
132
F.2.3 Autotest codes
Pre-programmed autotest sequences table (NL)
Autotest shortcut code 01 02 03 04 05
Description KL 1 ALG KL 2 ALG KL1 HEATERS
KL1
LEKSTROOM
KL3 ALG
Visual test
Earth bond
Output 200 mA
200 mA 200 mA
Limit
0.30
0.30
0.30
Time 5 s
5 s 5 s
Insulation
Output 500 V
500 V
Limit
1.00 M
0.25 M
Time 5 s
5 s
Insulation (probe)
Output
500 V
500 V
Limit
2.00 M
0.50 M
Time
5 s
5 s
Sub leakage
Output
40 V
Limit
7 mA
Time
5 s
Sub leakage (probe)
Output
Limit
Time
Differential leakage
Output
230 V
Limit
0.5 mA
Time
10 s
Touch leakage
Output
Limit
Time
Power
Output 230 V 230 V 230 V 230 V
Limit
Time 10 s 10 s 10 s 10 s
TRMS clamp current
Output
Limit
Time
Polarity test
RCD test
Mode
Type
Id RCD
Multi
Fase
Test