5.2 Measurements – Single tests for appliances
5.2.1 Earth bond resistance
This test ensures that the connections between the protective conductor terminal in the
mains plug of the DUT and earthed accessible conductive parts of the DUT (metal
housing) are satisfactory and of sufficiently low resistance. This test has to be
performed on Class 1 (earthed) DUT.
The instrument measures the resistance between mains test socket‘s PE terminal and
EB/S terminal.
Earth bond menu
Test parameters for earth bond resistance measurement
OUTPUT Test current [200 mA, 10 A]
LIMIT
Maximum resistance [0.1 0.9 , 1 9 ]
TIME Measuring time [2 s, 3 s, 5 s, 10 s, 30 s]
Test circuit for earth bond resistance measurement
Measurement of earth bond resistance of class I DUT
Earth bond resistance measurement procedure
Select the EARTH BOND function.
Set test parameters.
Connect device under test to the instrument.
Connect test lead to EB/S output on the instrument.
Connect EB/S lead to accessible metal parts of the device under test (see figure
above).
Press the START key for measurement.