MI 3310 / MI 3310A SigmaGT Measurements
49
Test circuits for insulation resistance measurement
Measurement of insulation resistance of Class I DUT
Measurement of insulation resistance of fixed installed DUTs of Class I
Insulation resistance measurement procedure
Select the Insulation function.
Set test parameters.
Connect device under test to the instrument (see figures above).
For fixed equipment:
Disconnect mains supply of the fixed equipment;
Connect LN test socket of the instrument to L/N terminals of the fixed equipment;
Connect PE test socket of the instrument to metallic enclosure of the fixed
equipment.
Press the START key for measurement.
Examples of insulation resistance measurement results
Displayed results:
Main result ............. Insulation resistance