User`s manual
MTEK6000 SERIES USER'S MANUAL 
January 2002  2-5 
PULSE INPUT TO THE MTEK6000 
Magnetically operated reed switches inside 
the meter drive assembly send electronic 
pulses as the drive turns. These pulses 
represent uncorrected meter volume to the 
instrument. 
To eliminate false counts that can result from 
the reed switch "bounceā, the MTEK6000 
uses a set/reset, dual-reed switch 
configuration. An input pulse is generated 
only when the opening and closing of the 
first switch is followed by the opening and 
closing of the second switch. The main 
counter input is also monitored for fault 
conditions. When enabled, if any of the dual-
reed switches should be defective, the input 
pulses will automatically switch to the 
working counter input and the MTEK6000 
will generate a Faulty Counter alarm. This 
function is enabled if the Counter Fault 
Monitoring parameter is set to 1 and 
disabled if set to 0. The default value is 0 for 
disable. See Appendix A for addressing. 
For units supplied with indexes, the main 
counter input is terminated at the UNIT 
(BLK) MTA connector and the uncorrected 
pulse wiring at the FIELD (WHT) MTA 
connector at the lower right hand corner of 
the corrector printed circuit assembly. 
Metretek, Inc. can supply a remote index 
similar to the main index or a sandwich 
pulser for wall or pipe mount installations. 
When the sandwich or external pulser option 
(1, 10, 20, or 50 pulse per revolution) is 
supplied, connect the N.O., COM, and N.C. 
wiring to terminals 32 (SET1), 33 (GND) and 
34 (RST1) respectively. 
The pulse input is software selectable for 
Form C (three-wire) or Form A (two-wire) 
connection. 
Software is used to configure the pulse input.  
The optional, external keypad / display can 
also be used to configure the pulse input and 
other parameters. See Appendix A for 
addressing. 
WALL AND PIPE MOUNTING 
The MTEK6000 can also mount directly on a 
wall or on a pipe. Mounting feet are provided 
for wall mounting. See Figure 2-5. 
For pipe mounting, approximately 10 feet of 
2-inch rigid iron pipe or conduit is required.  
The pipe should be installed 18 to 24 inches in 
the ground in 6 inches wide concrete. The 
length of the 2-inch mounting pipe or conduit 
will vary according to the site, but typical 
installations place the MTEK6000 at about 
eye level for ease of operation. Mounting 
plates are provided for pipe mounting. Secure 
the MTEK6000 to the pipe with the provided 
U-bolts, washers and hex nuts. See 
Figure 2-6. 










