MTEK6000 SERIES USER'S MANUAL 
January 2002  2-11 
Volume and Alarm Pulse Specifications 
1.   All pulse outputs are isolated from 
ground and each other. Provides 1,500 
volts between input and output and 
between contact sets. 
2.   Form C: DC load only, 125mWdc max, 
50Vdc max 
Form A: AC or DC load 800mW max, 
400V max., 100mA max, continuous 
3.   Configurable pulse width from 1 to 5,000 
milliseconds (ms). 
Uncorrected Mechanical Pulse Output 
(Units with a Metretek Index) 
The uncorrected mechanical pulse output is 
derived from the Form C reed switch in the 
index assembly. As the magnet in the drive's 
assembly rotates past the Form C switch, a 
single uncorrected volume pulse output is 
generated. Volume per pulse is determined 
by the drive rate. Each uncorrected volume 
pulse is equal to the gas flow for one shaft 
revolution. 
The pulse output can be wired as a Form A or 
Form C switch output. Use terminals 25 
(normally open), 24 (common) and 23 
(normally closed) for Form C output. To 
wire as Form A, use terminals 25 (normally 
open) and 24 (common) and make no 
connection to terminal 23 (normally closed).  
The duration (width) of each pulse is equal to 
the length of time the reed switch is in its 
closed position (depends on the rate of the 
meter). No configuration is necessary to 
enable the uncorrected mechanical pulse 
output. 
Uncorrected Pulse Output Specifications 
1.   3W contact rating (power dissipation). 
2.   Maximum switching voltage up to 30V. 
3.   Maximum switching current up to 200mA. 
4.   Maximum continuous current @ 500 mA. 
NOTE 
All pulse outputs are disabled in the standard 
unit to conserve power. The Alarm pulse 
output is a one time pulse output signal. No 
other alarm pulse will be generated until the 
alarm is cleared and becomes active again. 