User`s manual
 MTEK6000 SERIES USER'S MANUAL 
4 - 4   January 2002  
Therefore, 0% = 4mA, 25% = 
8mA, 50% = 12mA, 75% = 16mA, & 100% 
= 20mA. 
6.   If adjustments are needed, press zero. 
The display now shows: 
 zero: x.xxx 
 04.000 +y.yyy mA 
x.xxx represents the default zero value 
(low scale) and y.yyy is the adjustment 
made to 4mA for the analog output signal.  
The adjustment can either be positive or 
negative shown by + or - respectively. The 
top line will alternate between zero: x.xxx 
and UP/DN TO ADJUST. This is the zero 
adjusted value to calibrate the analog output 
to 4mA. 
7.   Press ↑ or ↓ to increase or decrease the 
output until the meter reads 4mA or the 
current zero reference matches the field 
equipment. Press ent to collect the new 
point. 
8.   Press span. The display shows: 
 span: x.xxx 
20.0 +y.yyy mA 
x.xxx represents the default span value 
(full scale) and y.yyy is the adjustment 
made to 20mA for the analog output 
signal. The adjustment can either be 
positive or negative shown by + or -  
respectively. The top line will alternate 
between span: x.xxx and UP/DN TO  
ADJUST. This is the span adjusted 
value to calibrate the analog output to 
20mA. 
9.   Press ↑ or ↓ to increase or decrease the 
output until the meter reads 20mA or the 
current span reference matches the field 
equipment. Press ent to collect the new 
point. 
10. Steps 5 - 9 are required only once. They 
may be repeated as often as necessary 
while in calibration, but only the most 
recent point will be saved on completion 
of calibration. 
11. To permanently store the results of the 
calibration press ent, and the unit will 
prompt  Enter to accept Calibration. 
Simply press ent again to save the 
calibration. Press esc to abort the 
calibration. 