User`s manual
 MTEK6000 SERIES USER'S MANUAL 
January 2002 C - 3 
Cubic Unit/Pulse In or Meter Drive 
This parameter determines the volume unit 
represented by one input pulse, and is 
normally set to equal the drive (CF/Rev) of 
the meter. Standard indexes produce one 
pulse per revolution; therefore, the CF/Pulse 
will equal the drive rate of the meter. The 
Default value is 100. 
For instruments utilizing remote pulsing 
devices, this value can also be determined by 
dividing the CF/Rev of the meter by the 
number of pulses per revolution generated by 
the remote pulser. 
For example: Consider a 3GT meter with a 
100 CF/Rev drive and a 50 Pulse/Rev Imac 
Pulsamatic Transmitter. The CF/Pulse is 
determined as follows: 
CF/Pulse = 100 CF/Rev * 1 Rev/50 Pulses 
   = 2 CF/Pulse 
NOTE FOR METERS WITH 5 CF/REV 
DRIVE RATES: 
Re-position the input compound gear to the 
correct position, and set this parameter to a 
value of 10. Refer to Section Two or contact 
Metretek, Inc. for assistance in positioning the 
compound gear. 
Current Day High Volume Alarm Reset 
After the Current Day's Total is exceeded, the 
setpoint at which the unit exits this condition 
is entered in this location. The Default value 
is 99,990. 
Current Day High Volume Alarm 
Setpoint 
This parameter specifies the setpoint at which 
the unit determines whether the Current Day 
Flow Total is in an alarm condition. For 
transport or interruptible customers, this 
parameter can be used to alarm when an 
account has exceeded a predetermined daily 
volume allocation. The Default value is 
100,000. 
Date (Month, Day, Year) 
This is the current Date in the unit 
(MMDDYY). It is updated on each process 
scan. 
Flow Rate Update Interval (s) 
This parameter determines how often the flow 
rate gets updated in the EFC. However, it has 
no control over Volume updates. Volume is 
updated every time the unit wakes up from 
the sleep mode or every 3-4 seconds if the 
unit is always awake. 
The Flow Rate Update Interval parameter is 
of the form XXX.YY.M where the integer 
portion (XXX) is the time interval in seconds 
between Flow Rate updates. The digits after 
the decimal point (YY.M) represent the zero-
flow period (i.e. the amount of time to wait 
without receiving pulses before generating a 
zero flow rate). The first two digits are 
minutes and the third digit (T) is a fraction of 
a minute. Thus, a two-minute zero-flow 
period would be entered as XXX.020, a ten 
minute period as XXX.10. The maximum 
allowed period is 27 minutes and the default 
is one minute (XXX.010). 
The user MUST specify a zero-flow period, 
which is larger than or equal to the Flow Rate 
Update Interval. Specifying a zero-flow 
period smaller than the Flow Rate Update 
Interval will result in a zero-flow rate being 
displayed even when there is an apparent 
flow. For example: A value of 600.11 would 
update flow rate every 10 minutes and display 
zero flow if 11 minutes passed without an 
input pulse. A value of 600.01 will not work 
properly. It would try to update flow rate 
every 10 minutes, but would zero the flow 
rate every minute, even if pulses come in 
faster than one per minute. 










