User's Guide

1.2. Safety
Please observe the following instructions:
Do not open the unit, except if so instructed by the Metrilog technical personnel!
Should it be necessary to open the unit (e.g., to replace the SIM card), the operation must be
executed only in a moisture free environment. You will need a Philips screwdriver size PH2. Note
that the screws remain attached to the lid, there is no need to remove them. Remove the lid slowly
and carefully, because an antenna is fixed on its back. The antenna cable goes to a connector on the
electronics board and it can be easily damaged. Before mounting the lid back, make sure the gasket
is properly seated! If the gasket is damaged, contact Metrilog for a replacement. A defective gasket
will lead to moisture entering the housing, thus permanently damage the unit.
Please make sure that all the cables and connectors are properly fasten to avoid moisture entering
the unit and/or the connectors.
During normal use outdoors, the dust cover attached to the unit must always be inserted into the
USB connector (see picture above).
If either the MPI or the SDI connector is not used, it must be covered with the attached protection
cap.
The unit can be powered on all three connectors, even simultaneously, in which case the power
source with the highest voltage will take precedence.
The minimum voltage is 6 Volt for the SDI and MPI connectors and 4.7 Volt for the USB connector;
the maximum voltage is 30 Volt for the SDI and MPI connectors and 5.3 Volt for the USB connector.
Under no circumstances should the maximum voltage be exceeded!
Improper commands issued through the USB port or over telnet, in particular commands modifying
certain attributes, may compromise the functionality of the RTU and may render it inoperable.
1.3. Information to Users in the US
This device is granted permission to be operated in the US under the FCC ID 2A6UM-M717D.
Any changes or modifications not expressly approved by the party responsible for compliance
could void the user's authority to operate the equipment.
FCC RF Exposure statement: This device contains a RF Transmitter that complies with FCC RF
radiation exposure limits set forth for an uncontrolled environment. This transmitter must be
installed to provide a minimum separation distance of at least 20 cm from all persons and must not
be co-located or operating in conjunction with any other antenna or transmitter, except in
accordance with FCC multi-transmitter product procedures.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
4