Sensor Scaling (continued):
14 = GWR Flat (used with GWR sensor on vertical wall tanks)
15 = GWR RndHrz (used with GWR sensor on round horizontal tanks)
16 = 2012 Horiz (small dial horizontal propane or fuel tank w/ dial produced before 1/13)
Tank Fill Threshold: The tank fill event qualification amount in percent full.
Min: 3%; Max: 95%
Default: 10%; Disable: 0%
Tank Draw Threshold: The tank draw event qualification amount in percent full.
Min: 3%; Max: 95%
Default: 15%; Disable: 0%
Critical High Threshold: The tank critical high condition level in percent full.
Min: 5%; Max: 95%
Default: 0%; Disable: 0%
Warning High Threshold: The tank warning high condition level in percent full.
Min: 5%; Max: 95%
Default: 0%; Disable: 0%
Warning Low Threshold: The tank warning low condition level in percent full.
Min: 5%; Max: 95%
Default: 30%; Disable: 0%
Critical Low Threshold: The tank critical low condition level in percent full.
Min: 5%; Max: 95%
Default: 15%; Disable: 0%
Level Change Threshold: The tank level change qualification amount in percent full. Set to
a negative number to track a tank level decrease; set to a positive number to track a tank
level increase.
Min: -95%; Max: +95%
Default: 0%; Disable: 0%; Invalid: +1 to +4%, -1% to -4%
Gain Adjust: Used to compensate for tank and gauge size mismatches and gauge gain
calibration errors. For special applications only - use with caution.
Min: -10.00x (Gain of -10.00); Max: +10.00x (Gain of +10.00)
Default: +1.00x (Gain of +1.00)
Disable: N/A; Invalid: +0.00
Offset Adjust: Used to compensate for gauge offset calibration errors.
For special applications only - use with caution.
Min: -100.00; Max: +100.00
Default: +0.00; Disable: N/A