Operating instructions METTLER TOLEDO MultiRange Application software IND690-Fill www.mt.
Congratulations on choosing the quality and precision of METTLER TOLEDO. Proper use according to these instructions and regular calibration and maintenance by our factory-trained service team ensure dependable and accurate operation, protecting your investment. Contact us about a ServiceXXL agreement tailored to your needs and budget. We invite you to register your product at www.mt.com/productregistration so we can contact you about enhancements, updates and important notifications concerning your product.
Contents IND690-Fill Contents Page 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 Dispensing functions ................................................................... Documentation ............................................................................. Introduction.................................................................................. Dispensing system ....................................................................... Dispensing process ....................................
Dispensing functions 1 IND690-Fill Dispensing functions 1.1 Documentation The weighing terminal IND690-… comes supplied with a CD containing all the documentation on the weighing system IND690. These operating instructions describe the operation and configuration of the application software IND690-Fill. The basic information for working with the weighing terminal IND690-... can be found in the operating instructions IND690-Base. 1.
Dispensing functions IND690-Fill 1.3 Dispensing system With feed valves or feed chutes controlled with coarse and fine feed, the dispensing sample is automatically infed up to the specified target value. The control signals for the feed valves are transmitted to the 8-690 relay box via the RS485-690 interface. The 8-690 relay box controls the dispensing system either directly or via an additional external control unit (PLC).
Dispensing functions IND690-Fill 1.
Dispensing functions IND690-Fill 1.5 Entering numerically Entering dispensing parameters 1. Press LIMIT key. 2. Enter target weight and confirm with ENTER. 3. Specify limits: enter ENTER LIMIT 1 and LIMIT 2 and confirm with ENTER. To automatically determine the limits, press ENTER without making an entry. 4. Specify tolerance: enter TOL and confirm with ENTER. 5. If tare checking is to be used, specify tare values TMIN and TMAX and confirm with ENTER.
Dispensing functions IND690-Fill Notes • For the application BELOW LEVEL/BELOW BUNGHOLE, NOZZLE CONTROL ON two 8-690 relay boxes must be connected. • During the filling process exactly one of the signals NOZZLE DOWN / MIDDLE / UP has to be active. Otherwise the error message SEVERAL INPUTS ON or WAITING FOR INPUT is displayed. The filling process is not continued until exactly one of these signals is active.
Dispensing functions IND690-Fill 1.6.2 Dispensing with filling container on the weighing platform During dispensing the filling container on the weighing platform is filled from a supply vessel. 1. Enter dispensing parameters, see section 1.5. The display shows READY FOR DISPENSING. 2. Place empty filling container on the weighing platform. 3. Press START key. The display shows the following: weight value, dispensing status and DeltaTrac.
Dispensing functions IND690-Fill 1.6.3 Dispensing with a supply vessel on the weighing platform During dispensing the filling container is dispensed from a supply vessel on the weighing platform. 1. Enter dispensing parameters, see section 1.5. The display shows READY FOR DISPENSING. 2. Place filled supply vessel on the weighing platform. 3. Press START key. The display shows the following: weight value with negative sign, dispensing status and DeltaTrac.
Dispensing functions IND690-Fill 1.9 Redispensing If, for example, the weight value is briefly exceeded, the fine feed is switched off too early and the current weight value (actual value) is below the target value. During redispensing the fine feed is opened in intervals until the target value is reached. Depending on the setting in the master mode, redispensing is carried out manually or automatically, see section 2.2. Manual redispensing Prerequisite MANUAL REDISPENSING is set in the master mode.
Dispensing functions IND690-Fill 1.11 Totalizing automatically To automatically totalize dispensing processes with the same dispensing samples, an item counter can be specified which determines the number of dispensing processes. When the item counter reaches its stop value, the dispensing system stops automatically. Prerequisite TOTALIZING ON is set in the master mode. 1. To set the item counter: – Press N key. – Enter start value of item counter and confirm with ENTER.
Dispensing functions IND690-Fill 1.12 Recalling application-specific information Information on dispensing can be recalled with the following key combinations: INFO, N INFO, SUM INFO, LIMIT INFO, fixed target number, LIMIT Display item counter. Display current weight sum. Display current dispensing parameters. Display stored dispensing parameters. Notes • If several pieces of information are recalled with one key, the display changes automatically after the set DISPLAY DURATION.
Settings in the master mode 2 IND690-Fill Settings in the master mode 2.1 Overview of the PAC master mode block The following system settings can be entered in this block: Legend • Blocks on a grey background are described in detail in the following. • Factory settings are shown in bold print. • Blocks which only appear under certain conditions appear with a dotted outline.
Settings in the master mode IND690-Fill 2.2 Settings in the PAC master mode block Note You can make all master mode adjustments conveniently with the PC using the FillTool software. Ask your METTLER TOLEDO sales partner. See section 2.2.6 for examples. APPLICATION Select application ABOVE LEVEL Dispensing above the filling level (factory setting) BELOW LEVEL Filling with dispensing lance below the dispensing level NOZZLE CONTROL Switch nozzle control on or off.
Settings in the master mode AUTOMATIC TARE IND690-Fill Switch automatic taring before dispensing on or off Factory setting: AUTOMATIC TARE ON REDISP. CORRECTION Switch redispensing correction on or off The redispensing correction function optimizes the switch-off point of the fine feed (limit 2). If REDISP. CORRECTION ON is set, the target-actual difference is determined for each container and multiplied by a FACTOR.
Settings in the master mode IND690-Fill FIXED TARGET Save dispensing parameters for various components in target memories protected against power failure LOAD FIXED TARGET 1. Enter FIXED TARGET NO. memory number: 1 … 999. 2. Enter article designation NAME, e.g. M8 SCREW. 3. Enter TARG target weight. 4. If OUTPUT 2 = 3RD SHUTOFF POINT: Enter switchover point preflow/coarse feed LIMIT 0. 5. Enter coarse/fine feed switchover point LIM 1. 6. Enter switch-off point of fine feed LIM 2: LIMIT 1 ≤ LIMIT 2. 7.
Settings in the master mode TOTALIZING IND690-Fill Switch automatic totalizing on or off If TOTALIZING ON is set, the dispensings to be totalized can be selected. Factory setting: TOTALIZING OFF CORRECT DISPENSINGS Only totalize dispensings within the tolerances. Cancelled dispensings can be added to the total sum with the SUM key in the CONTINUE WITH START state. ALL DISPENSINGS Totalize all dispensings.
Settings in the master mode IND690-Fill OPERATING MODE Set operating mode with certified weighing platforms NON AUTOMATIC The dispensing process does not run automatically and the permissibility of the weight values must be monitored by the operator. AUTOMATIC The dispensing process runs automatically (factory setting). Comments • Different national tolerances are taken into account.
Settings in the master mode LEARN MODE IND690-Fill Switch Learn mode on or off If LEARN MODE ON is set and the dispensing parameters are entered without limits or limit 2 ≤ limit 1, the IND690-Fill determines the valve switch-off points limit 1 and limit 2. If LEARN MODE OFF is set, limit 1and limit 2 must be entered manually.
Settings in the master mode IND690-Fill MONITOR DISPENSING Switch monitor dispensing on or off Dispensing monitoring monitors the weight increase in each measuring cycle. If MONITOR DISPENSING ON is set and the weight value exceeds or drops below the SENSITIVITY value, dispensing monitoring is activated.
Settings in the master mode IND690-Fill MONITOR DISPENSING Switch monitor dispensing on or off Example Big bag emptying If SUBTRACTIVE WEIGHING ON is selected, the dispensing monitor stops the emptying process as soon as the big bag is fully emptied. The last filling process is generally not yet complete here. The previously removed weight can be saved by pressing the TARE key. After inserting a new big bag and pressing the START key, the interrupted filling process is then completed.
Settings in the master mode IND690-Fill START TIMER Set delay time between the start of the dispensing process and opening of the coarse feed TIME Possible values: 0 … 999 seconds (factory setting: 0) Comments • When the start timer is activated, the display shows the time remaining. • The start timer can be interrupted or cancelled with the STOP key. • If two 8-690 relay boxes are installed, the OUT7 output on the second 8-690 relay box is set to HIGH during the delay time.
Settings in the master mode SINGLE FEED OPERATION IND690-Fill Switch single feed operation on or off If SINGLE FEED OPERATION ON is set and the target value of the specified LIMIT is dropped below, dispensing is then only carried out with fine feed. This also enables smaller quantities to be dispensed without switching over the dispensing system (valves, pumps). Factory setting: SINGLE FEED OPERATION OFF LIMIT Enter threshold value for single feed operation.
Settings in the master mode IND690-Fill RESET PAC Reset all functions to the factory settings Block APPLICATION AUTOMATIC TARE REDISP.
Settings in the master mode 2.2.1 IND690-Fill Material agitation MATERIAL AGITATION Switch agitator in dependence on weight and time LIMIT 1, LIMIT 2, TARGET VALUE LIMIT 1, LIMIT 2 or TARGET VALUE are reference quantities for the material agitation. Possible settings: WEIGHT + TIME • WEIGHT: Enter switch-on value as difference to the reference quantity. • TIME: Enter switch-on time between 0 … 9999 seconds; The dispensing process is interrupted during the switch-on time.
Settings in the master mode IND690-Fill 2.2.3 FILL QUANTITY Fill quantity Set fill quantity control during weighing-out If the gross weight of the filling container drops below a specified value ALARM VALUE after a dispensing process, output OUT2 on the first 8-690 relay box is set to HIGH. The supply vessel is automatically refilled and the display shows REFILL. When the specified weight value FILL QUANTITY is reached, output OUT2 is set to LOW.
Settings in the master mode 2.2.4 IND690-Fill Weighing platform switchover SCALE SWITCHOVER Switch back and forth between two weighing platforms MANUAL Manual switchover with a pulse at input IN 6 of the first 8-690 relay box. AUTOMATIC Switch over automatically. WEIGHING-IN If ACKNOWLEDGE OFF is also set and the output OUT6 (End of Dispensing) on the first 8-690 relay box is connected to the input IN 2 (Start), the dispensing process and change run automatically.
Settings in the master mode IND690-Fill 2.2.5 3RD SHUTOFF POINT 3rd shutoff point Control of a third valve Dispensing systems with 3 valves have a 3rd shutoff point (limit 0), which is controlled via output 2. Up to limit 0 (switchover point preflow/coarse feed) dispensing is carried out with preflow. Comments • The learn mode is automatically switched off an all 3 limits must be manually entered. • Limit 0 may not be entered greater than limit 1.
Settings in the master mode 2.2.6 IND690-Fill FillTool FillTool is a free configuration and editing tool for IND690-Fill which runs on every PC. It communicates with the IND690-Fill via a serial interface or Ethernet/WLAN and enables convenient configuration and data management, monitoring and conversion from and to ACCESS databases. Please ask METTLER TOLEDO Customer Service about FillTool.
Settings in the master mode IND690-Fill Editing fixed target entries Fixed target entries can be edited easily with FillTool.
Application blocks 3 IND690-Fill Application blocks In the following description, the application blocks are shown in the syntax for the MMR command set. When used with the SICS command set, please observe the SICS conventions, see Operating instructions for IND690-Base weighing terminal. No. Content Format 301 Pac version Response: {A[B|_|IND690-Fill_Vx.
Application blocks IND690-Fill No. Content Format 315 Correction factor for redispensing correction Response: Write: {A[B|_|Factor (0.0 … 0.9; step size 0.1)} {A[W|3[1[5|_|Factor (0.0 … 0.9; step size 0.
Application blocks IND690-Fill No.
Application blocks IND690-Fill No. Content Format 359 Status of output 2 Response: 360 Items poor (items outside tolerance) Operating instructions 22012836B 09/08 Write: {A[B|_|Code (Number_4)}, e.g.
Application blocks IND690-Fill No. Content Format 361 Dispensing state Response: Write: {A[B|_|Code (number_3)}, e.g.
Application blocks IND690-Fill No. Content Format 362 Sensitivity of dispensing monitoring Read: Write: {A[B|_|Number_12} {A[W|3[6[2|_|Number_12} 363 Trip factor coarse feed in learn mode Read: Write: {A[B|_|Factor (0.1 … 0.9; step size 0.1)} {A[W|3[6[3|_|Factor (0.1 … 0.9; step size 0.
What to do if …? 4 IND690-Fill What to do if …? Error / Display Possible causes Remedy – EMPTY – • Output 2 = Remaining quantity, container is automatically emptied ➜ Wait until the container is empty – REFILL – • Output 2 = Fill quantity, container is refilled ➜ Wait until the fill quantity is reached – TARE – • Automatic taring during start of dispensing process ➜ Wait until scale is stabilized and tared NOT ZERO • Below-level dispensing: Nozzle has run dry ➜ Prevent nozzle from running
What to do if …? IND690-Fill Error / Display Possible causes Remedy TMAX LESS THAN TMIN • Maximum tare value is less than minimum tare value ➜ Increase max. tare value and decrease min. tare value TOLERANCE INADMISS.
Technical data 5 IND690-Fill Technical data Dispensing functions Dispensing • Controlling of coarse and fine flow of material feed for liquid, pasty and pourable weighing samples • Learn mode: automatic determination of dispensing parameters (coarse and fine feed) • Redispensing correction: Optimization of the fine-feed shutoff point (limit 2) • Tolerance check with automatic redispensing • Manual redispensing via keypad • Differentiation between below- and above-level dispensing • Control of elements
Appendix IND690-Fill 6 Appendix 6.1 Connection diagram and terminal assignment for 8-690 relay box Note The first 8-690 relay box can also be replaced with 4 I/O-690 interfaces and 4-690 relay boxes. 1st relay box 4-690 on COM6 IN1 ... IN4 OUT1 ... OUT4 2nd relay box 4-690 on COM5 IN5 ... IN8 OUT5 ... OUT8 Operating instructions 22012836B 09/08 Terminal 2, IN0 ... IN3 Terminal 3, OUT0 ... OUT3 Terminal 2, IN4 ... IN7 Terminal 3, OUT4 ...
Appendix IND690-Fill First 8-690 relay box Assignment with factory setting. For individual assignment, see CONFIGURATION OF INPUTS AND OUTPUTS in master mode of relay box 8 or 4 I/O.
Appendix IND690-Fill Second 8-690 relay box Assignment with factory setting. For individual assignment, see CONFIGURATION OF INPUTS AND OUTPUTS in master mode of relay box 8 or 4 I/O.
Appendix IND690-Fill 6.2 6.2.
Appendix IND690-Fill NOZZLE CONTROL ON and DRIP PAN ON The following sequence chart shows the assigned inputs and outputs of the second 8-690 relay box. The first 8-690 relay box is assigned in accordance with the flow chart "NOZZLE CONTROL OFF and DRIP PAN OFF", with the exception of the sequence monitoring for the nozzle (IN1, IN2).
Appendix IND690-Fill 6.2.
Index IND690-Fill 7 Index A Acknowledge 22 Automatic tare 16 C Coarse feed 22 D Dispensing 7 Dispensing functions 4 Dispensing parameters 7 Dispensing system 5 T Target memory 7, 17 Technical data 40 Totalizing 12, 18 W What to do if …? 38 Z Zero zone 15 E Electronic finger 5 End timer 23 Error messages 38 F Fill quantity 19 Function keys 4 I Item counter 4, 12 L Learn mode 6, 20 Limit 0 29 M Manual recorrection 11, 19 Material agitation 19 Monitor dispensing 21 O Operating mode 19 Outputs 19, 24 P Pa