Operating instructions
Settings in the master mode
24 Operating instructions 22012836B 09/08
IND690-Fill
SINGLE FEED
OPERATION
Switch single feed operation on or off
If SINGLE FEED OPERATION ON is set and the target value of the specified LIMIT is
dropped below, dispensing is then only carried out with fine feed. This also enables
smaller quantities to be dispensed without switching over the dispensing system
(valves, pumps).
Factory setting: SINGLE FEED OPERATION OFF
LIMIT Enter threshold value for single feed operation.
OUTPUT 7 Set switch-on of the OUT 7 output to the first 8-690 relay box
IMPULSE ON START OUT 7 is briefly switched on during the start-up of the IND690-Fill (factory setting).
ON AT STATUS X YYY Enter up to 30 dispensing states for which OUT 7 is switched on. X is the serial
number (1 ... 30), YYY is the code for the various dispensing states (000 ... 254),
see application block 361 on page
36.
To end the input of the dispensing states, press ENTER without making an entry.
ANALOG OUTPUT Output throughput at analog output
When ANALOG OUTPUT ON is set, a respective throughput (0 ... 99 %) is output at
an integrated analogue output during the opening of the preflow, coarse feed or fine
feed.
The size of the throughput can be entered manually with the LIMIT key or with a port
via the application blocks 322 ... 347 or 323_001 ... 323_999.
Factory setting: ANALOG OUTPUT OFF
Note For this purpose, the analog output must be configured as follows:
Start-Stop mode
BLOCK NUMBER 366
START VALUE 0 kg
STOP VALUE Maximum load of weighing platform
START V/MA as required
STOP V/MA as required
READY PIN INPUT Setting the logic for the stand-by signal
LOW ACTIVE The READY signal has to be configured for a digital input to this purpose.
This signal is used to stop the filling process when the signal that can be switched in
the logic between LOW ACTIVE (factory setting) and HIGH ACTIVE is no longer
recognized.
The stopped dispensing process has to be reactivated by pressing a key (START).
HIGH ACTIVE