Owner Manual

Catalyst Owner’s Manual | © MF Fire 2017 Page | 10
Stove Placement Requirements
Catalyst must be placed in a room with a source of fresh air.
Stove must be placed so that no combustibles are within, or can swing
within 36" (914mm) of the front of the stove (drapes, doors, etc.).
Floor protection must extend around the front, sides, and rear of the
stove, according to listed clearance requirements below. Floor
protection must be made of a non-combustible material and at least
0.018” (0.45 mm) thick with a minimum R-value of 2.67 ft2•hr•°F/Btu/in.
Catalyst must also maintain the following minimum clearances to
combustibles (drywall, furniture, etc.):
Minimum Clearance Requirements
A Side wall to stovetop
20” (508 mm)
B Back wall to stovetop
12” (305 mm)
C Corner wall to stovetop
8” (203 mm)
D Connector to side wall
30” (762 mm)
E Connector to back wall
15” (381 mm)
F Connector to corner wall
18” (458 mm)
G Floor protection, side and back
8” (203 mm)
H Floor protection, front
I Floor protection, connector side
J Back wall to electronic enclosure
16” (407 mm)
2” (51 mm)
12” (305 mm)