Specifications

Power-Zone
®
4
Dimensions
85
11/2005
© 2005 Schneider Electric All Rights Reserved
Figure 58: Front Elevation Dimensions–Not for Construction (consult factory drawings)
91.50
2324
36.00
914
A
CD
B
Typical Feeder Circuit Breakers–D
(36-inch wide)
91.50
2324
36.00
914
AB
CD
Typical Feeder Circuit Breakers–E
(36-inch wide)
91.50
2324
22.00
559
B
D
A
C
Typical L1 Main and Tie Circuit
Breakers–A (36-inch wide)
91.50
2324
36.00
914
A
D
BC
Typical L1 Feeder Circuit
Breakers–A (22-inch wide)
Table 17: Typical Feeder–D (36-inch wide)
Location Description
Frame
Size
Frame
SCCR
A Feeder 800 A–2000 A N1–H2, L1F
B Feeder 800 A–2000 A N1–H2, L1F
CD Feeder 4000 A–5000 A H2
Table 18: Typical Feeder–E (36-inch wide)
Locatio
n
Description
Frame
Size
Frame
SCCR
AB Feeder 4000 A–5000 A H2
CD Feeder 4000 A–5000 A H2
Table 19: Typical L1 Main and Tie–A (200
kA @ 480 V) (36-inch wide)
Location Description
Frame
Size
Frame
SCCR
A
Blank or
instrument
––
BC Main or tie 2000 A–5000 A L1
D Feeder 2000 A L1, L1F
Table 20: Typical L1 Feeder–A (200 kA @
480 V) (22-inch wide)
Location Description
Frame
Size
Frame
SCCR
A Feeder 800 A–2000 A L1, L1F
B Feeder 800 A–2000 A L1, L1F
C Feeder 800 A–2000 A L1, L1F
D Feeder 800 A–2000 A L1, L1F
NOTE: Any main, tie, or feeder compartment positions may
be used as a blank, or instrument compartment. Not
convertible for future circuit breaker use.Height including
secondary wiring trough compartment is
93.7 inches (2380 mm).