UPS Module Specifications
100 kVA 130 kVA 150 kVA
Input Voltage (V) 208 480 480 600 208 480 480 600 208 480 480 600
Output Voltage (V) 208 208 480 600 208 208 480 600 208 208 480 600
Nominal Input Current (A) 311 135 135 108 414 180 180 144 483 210 210 168
Maximum Input Current (A) 343 149 149 119 455 198 198 158 531 231 231 185
Nominal Output Current (A) 278 279 121 97 361 361 157 126 416 418 181 145
DC Current at Nominal Voltage (A) 219 283 331
Efficiency at 100% 92.5% 93% 93%
Full Load Heat Rejection (BTUs) 25600 31060 35840
UPS Module Weight (lbs) 3050* 3050* 3050*
Module Width (75”H x 33”D) 48” 48” 48”
180 kVA 200 kVA 225 kVA
Input Voltage (V) 208 480 480 600 208 480 480 600 208 480 480 600
Output Voltage (V) 208 208 480 600 208 208 480 600 208 208 480 600
Nominal Input Current (A) 600 260 260 208 692 300 300 240 692 300 300 240
Maximum Input Current (A) 660 286 286 229 738 320 320 256 738 320 320 256
Nominal Output Current (A) 501 501 217 174 556 556 241 217 625 625 271 217
DC Current at Nominal Voltage (A) 392 438 442
Efficiency at 100% 93% 93.5% 93.5%
Full Load Heat Rejection (BTUs) 43000 44370 45000
UPS Module Weight (lbs) 3050* 3050* 3050*
Module Width (75”H x 33”D) 48” 48” 48”
*
UPS module only~does not include transformer and auxiliary cabinets
MGE UPS SYSTEMS THE UNINTERRUPTIBLE POWER PROVIDER
www.mgeups.com
info@mgeups.com
GX PW 100
Effective: October 2002
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.
ARGENTINA
Thames 91
1609 San Isidro
Prov de Buenos Aires
tel (54) 11-4766-8777
fax (54) 11-4766-6008
USA (headquarters)
1660 Scenic Avenue
Costa Mesa, CA 92626
tel (800) 523-0142
(714) 557-1636
fax (714) 557-9788
CANADA
#9, 2798 Thamesgate Dr.
Mississauga, ON L4T 4E8
tel (905) 672-0990
(877) 672-0990
fax (905) 672-7667
BRAZIL
Avenida Guido
Caloi 1985 (GALPAO 23)
Guarapiranga
Sao Paulo - SP, CEP 05802
tel (55) 11-5891-2274
fax (55) 11-5890-3353
MEXICO
Ave. Congreso de la
Union
#524 Colonia Santa Anita
Mexico D.F 08300
tel 525 538 9687
fax 525 530 7625
N
A
B
C
G
L1
L2
L3
G
L1
L2
L3
QF1 QF1 QF1QF1
INPUT
ISOLATION
Tra ns fo rme r
(OPTIONAL)
INVERTER
STATIC
SWITCH
CHARGER
G
+
BATTERY
OUTPUT
FUSES
Q1
L1L2
INPUT
FUSES
STATIC
SWITCH
OUTPUT
ISOLATION
Tra ns fo rme r
(OPTIONAL)
G
+
BATTERY
FROM
UTILITY
INPUT
TO
CRITICAL
LOAD
I/0
CABINET
(OPTIONAL
with Input or
Output
Tra ns for me rs )
UPS MODULE
INPUT
FILTER
Q4S
K4S
Q5N
Q38P
BYPASS
N
A
B
C
G
L1
L2
L3
L3
Galaxy PW Battery Systems ~ Backup time in minutes at 100% load @ 0.8 power factor
Qty. Cabinets Weight (lbs) 100 kVA 130 kVA 150 kVA 180 kVA 200 kVA 225 kVA CB Rating
0.8 PF 0.9 PF 0.8 PF 0.9 PF 0.8 PF 0.9 PF 0.8 PF 0.9 PF 0.8 PF 0.9 PF 0.8 PF 0.9 PF
13,070 10 8 7 5 n/a n/a n/a n/a n/a n/a n/a n/a 250 A
26,140 30 26 22 17 16 13 12 10 10 8 8 6 250 A
39,210 50 44 35 30 30 25 22 19 20 17 16 13 250 A
4 12,280 75 64 50 44 41 36 35 30 30 26 26 21 250 A
13,734 17 14 11 9 9 7 6 n/a 5 n/a n/a n/a 250 A
27,468 41 35 30 26 25 22 20 17 17 14 14 12 250 A
3 11,202 74 62 50 43 42 37 33 28 30 26 24 22 250 A
4 14,936 105 93 75 64 60 53 48 42 42 37 36 33 250 A
14,770 23 19 15 12 12 9 8 5 6 n/a n/a n/a 400 A
29,540 59 52 42 36 36 31 28 23 24 20 19 16 400 A
3 14,310 100 87 74 61 59 52 46 41 41 35 37 31 400 A
4 19,080 135 120 100 88 85 74 68 59 60 52 51 44 400 A
Single Line Diagram
(single and parallel models)
Standard Features
IGBT/PWM Inverter
Low kVAR Input Filter
LED Mimic Diagram
Guided Operator Interface
Advanced Battery Management System
Modular Power Assemblies
Front Access Design
Computer Aided Self Diagnostics
RS2323/485 Serial Interface
Dry Contact Relay Status Array
Top to Bottom Access Models
AC Electrical Characteristics
Output Power Factor: >
0.9
Input Source: 208, 480, 600VAC 3PH,
3W + G (or 4W + G for Bypass)
Output: 208, 480, 600VAC 3PH,
3W + G, or 4W + G
Input Frequency Window: 60Hz/+
10%
Inverter Sync. to Bypass: +
0.5 Hz
(adjustable from +
0.25 Hz to + 2 Hz)
Input THDI: < 7.5% at 225 kVA
Voltage Transient Response
(at 100% Step Load): +
2%
Inverter Overload Capacity (A): 150%
for 1 min.; 125% for 10 min.
Bypass Instant Overload (1 cycle):
22 times nominal current
THDV (linear loads): < 1.5% Ph/Ph,
< 2.0% Ph/N
THDV (non-linear loads): < 2.0% Ph/Ph,
< 3.0% Ph/N
Input Switch Q1: 400 A
Bypass Input Contactor: 265 A (350 IEC)
Bypass Switch(es) Q4S/Q38P/Q5N:
400A
DC Electrical Characteristics
DC Nominal Voltage: 480 VDC
Max. DC Float Voltage: 545 VDC
Min. DC Cut-Off Voltage: 390 VDC
Environmental Characteristics
Storage Temperature Range: -
25ºC to +70ºC
Operating Temperature Range:
0ºC to 40ºC
Relative Humidity: 95% maximum
Noise Level (dBA): 68
Battery System Features
Individual cabinet dimensions: 75” H x 50” W x 33” D Run time specifications are for 77 °F/25 °C and may differ with temperature
All cabinets have a standard internal battery disconnect Longer duration battery banks and wet cell batteries are available on request
Cabinets may be ordered adjacent to the UPS or Above battery systems are housed in a matching enclosure
remote available upon request
All batteries specified above are sealed, low maintenance cells