Specifications

Switchboards
1199 ‡For prices refer to List Price Book K-13
K
Switchboards
N
Notes:
1. CK breakers have electronic trips only.
2. CJL and CJM are available with optional electronic trips (with suffix -T, -TA, -TG, -TAG, see section I for more information).
3. For 100% rated CK breakers, add 15% to breaker price list. (800A max)
4. Above prices include mounting hardware and installation.
5. For replacement branch breaker and mounting hardware prices, see Section I.
Type Amps Poles
Interrupting Capacity
Mounting Branch Height List Price ‡
240 Vac 480 Vac 600 Vac 250 Vdc
CJL400E
300-400A 3 65 kA 35 kA 25 kA 10 kA DOUBLE 4X
CJL400E-T
CJL400E-TA
CJL400E-TG
CJL400E-TAG
CJL400N
300-400A 3 100 kA 65 kA 35 kA 22 kA DOUBLE 4X
CJL400N-T
CJL400N-TA
CJL400N-TG
CJL400N-TAG
CJL400H
300-400A 3 200 kA 100 kA 50 kA 22 kA DOUBLE 4X
CJL400H-T
CJL400H-TA
CJL400H-TG
CJL400H-TAG
CJM..E
300-600A 3 65 kA 35 kA 25 kA 10 kA SINGLE 12X
CJM..E-T
CJM..E-TA
CJM..E-TG
CJM..E-TAG
CJM..N
300-600A 3 100 kA 65 kA 35 kA 22 kA SINGLE 12X
CJM..N-T
CJM..N-TA
CJM..N-TG
CJM..N-TAG
CJM..H
300-600A 3 200kA 100kA 50kA 22 kA SINGLE 12X
CJM..H-T
CJM..H-TA
CJM..H-TG
CJM..H-TAG
CMH
300-600A
3 65 kA 65 kA 25 kA 14 kA SINGLE 16X700-800A
900-1000A
CK400E
200-400A 3
42 kA 35 kA 25 kA
- SINGLE 12XCK400N 65 kA 50 kA 35 kA
CK400H 100 kA 65 kA 42 kA
CK800E
400-800A 3
42 kA 35 kA 25 kA
- SINGLE 12XCK800N 65 kA 50 kA 35 kA
CK800H 100 kA 65 kA 42 kA
CK1200E
600-1200A 3
42 kA 35 kA 25 kA
- SINGLE 12XCK1200N 65 kA 50 kA 35 kA
CK1200H 100 kA 65 kA 42 kA
TH1 15-100A 3 200 kA 200 kA 200 kA 100 kA DOUBLE 6X
TH4
70-225A
3 200 kA 200 kA 200 kA 100 kA SINGLE 12X
250-400A
TH8
300-600A
3 200 kA 200 kA 200 kA 100 kA SINGLE 12X
700-800A
Switchboard Branch Devices, Multi-pole MCCB's (continued)