Specifications

Switchboards
K-14 ‡For prices refer to List Price Book 1199
K
Switchboards
Notes:
1. Above prices include mounting hardware and installation.
2. Twin pole breaker has one common line connection and two separate load connections.
Notes:
1. Utility meter not included.
2. T-fuse kit available for 100A and 200A only.
Poles Lug Size
Interrupting Capacity
Catalogue No. Type List Price ‡
347 Vac 277 Vac 120/240 Vac
1
(1) #14 - #6 Cu/Al
14 kA 14kA 42 kA HEW0015 Std. Single
14 kA 14 kA 42 kA HEW0020 Std. Single
14 kA 14 kA 42 kA HEW1515 Twin
2
14 kA 14 kA 42 kA HEW2020 Twin
2
25 kA 65 kA 100 kA HEZ0015 Std. Single
25 kA 65 kA 100 kA HEZ0020 Std. Single
25 kA 65 kA 100 kA HEZ1515 Twin
2
25 kA 65 kA 100 kA HEZ2020 Twin
2
(1) #14 - 1/0 Cu/Al
18 kA 25 kA 25 kA CE1015E Std. Single
18 kA 25 kA 25 kA CE1020E Std. Single
18 kA 25 kA 25 kA CE1030E Std. Single
25 kA 65 kA 65 kA CE1015N Std. Single
25 kA 65 kA 65 kA CE1020N Std. Single
25 kA 65 kA 65 kA CE1030N Std. Single
Max. Volts Amps Catalogue Number Maximum Wire Size Branch Height Fuse Type Poles List Price ‡
600 Vac
250 Vdc
30-30 QMQB3336B (1) #6 Cu/Al
8X J, T
3
3
60-60 QMQB6636B (1) #2 Cu/Al
100-100 QMQB1136B (1) 1/0 Cu/Al
200 QMQB2036B (1) 250 MCM Cu/Al 14X
H, R, J, T400 QMQB4836B
(1) 750 MCM or (2) 500 MCM or
(3) 300 MCM or (4) 3/0 Cu/Al
24X
600 QMQB7036B
800 QMQB8836B (2) 750 MCM or (3) 500 MCM Cu/Al 28X
L,T1200 QMQB9836B
(4) 750 MCM Cu/Al 54X
1200 c/w Shunt Trip QMQB9836BS
Max. Volts Amps Maximum Wire Size Catalogue No. Branch Height Fuse Type Poles List Price ‡
600 Vac
250 Vdc
30-30 (1) #6 Cu/Al MQS7-3336B
14X J,T
2
3
60-60 (1) #2 Cu/Al MQS7-6636B
100-100 (1) 1/0 Cu/Al MQS7-1136B
200 (1) 250 MCM Cu/Al MQS7-2036
Switchboard Branch Devices, Single Pole MCCBs
200A (SINGLE)30A : 30A (TWIN)
Switchboard Branch Devices, QMQB Switches
Notes:
1. Above prices include cost of installation. See page D-16 for replacement units.
2. Prices do not include fuses. See Section E for fuse prices.
3 30A-100A units shipped in class J fuse configuration only. T-fuse kit available for
100A only.
4. 200A to 600A units are shipped in class J fuse configuration only. Please specify
type of fuse required.
5. 800A and 1200A units are shipped in Class L configuration only. Please specify
when Class T fuse is required.
6. 1200A Class T fuse available for 240V system only.
Switchboard Branch Devices, MQS Branch Utility Metering Switches