Product Description
INTRODUCTION
Power-Zone
®
4 low voltage, metal-enclosed, drawout switchgear is designed to provide superior
electrical distribution, protection, and power quality management for the entire facility. The prime
components of the switchgear are the Masterpact
®
NW and Masterpact NT ANSI-rated circuit
breakers. Power-Zone 4 switchgear is designed to maximize the functionality of the Masterpact NW
and NT circuit breakers, which, in turn, deliver maximum uptime, system selectivity, ease of
maintenance and circuit protection. All of this in the smallest footprint available for low voltage drawout
switchgear.
Features and Benefits
Power-Zone 4 is designed and built to
ANSI
®
C37.20.1 and is listed to UL
®
1558.
Masterpact NW and NT drawout low
voltage power circuit breakers are
designed and built to ANSI C37.13 and
C37.16., and are listed to UL1066.
Short-circuit current rating up to 200 kA
without fuses.
High short-time withstand ratings up to
100 kA for 30 cycles.
Family of field installable and
upgradeable Micrologic
®
trip units with
optional Powerlogic
®
data
communications features.
Smallest equipment footprint available
in this product class.
Front access to control and
communications wire connections.
Bolted copper bus provided as standard
(up to 5000 A maximum).
Large rear cable compartment pull area
allows maximum room for power
cables.
Bus provision for future equipment
expansion.
System designed for maximum uptime
with low maintenance.
Modular circuit breaker design for easy
addition of control accessories.
Figure 2: Through-the-Door
Access
Figure 3: Circuit Breaker
Compartment with
Secondary
Horizontal and
Vertical Wireways
Figure 1: Power-Zone 4
S
witchgear
Figure 4: Powerlogic System
Manager Software
Figure 7: Family of Masterpact NW Circuit
Breakers
Figure 5: Family of
Micrologic
Trip Units
Figure 6: Masterpact NT
Circuit Breaker