Micrologic
®
Trip Units
A new family of field-installable trip units is available with Masterpact
®
NW and NT circuit breakers.
The circuit breaker overcurrent protection consists of a solid-state, microprocessor-based tripping
device that requires no external power source. The complete tripping system has three main
components: the molded sensors, the trip device (with rating plug), and the trip actuator. The
microprocessor-based trip unit uses true RMS current level sensing. For additional information, refer to
the trip unit functionality matrix on page 41.
When a Masterpact NW or NT circuit breaker is closed, no external power is required for the protection
system. The trip unit is powered by current signal levels and current sensors integrally mounted in the
Masterpact NW or NT circuit breaker. All trip units are UL Listed for use in Masterpact NW or NT circuit
breakers.
Basic Trip Unit
S
tan
d
ar
d
T
r
i
p
F
eatures:
True RMS sensing
LI trip configuration
Field interchangeable long-time rating
plugs
LED long-time pickup indication
Thermal imaging
A
va
il
a
bl
e
O
p
ti
ons:
LSI trip configuration
Test kits
Standard Trip Features:
True RMS sensing
LI trip configuration
Field interchangeable long-time
rating plugs
LED long-time pickup indication
LSIG trip configurations
Digital ammeter–phase and
neutral
Phase loading bar graph
LED trip indication
Zone selective interlocking (ZSI)
with short-time and ground fault
Thermal imaging
Available Options:
LSI trip configuration
LSIG (ground fault trip)
Test kits
Available Powerlogic
®
Features:
Amps metering
Circuit breaker open/close trip
status
Tripping curves
Type A (Ammeter) Trip Unit
Micrologic Basic Trip
Unit
Micrologic Type A Trip
Unit