- MGE Installation and User Manual UPS EX 5/7/11RT

Installation and User Manual
Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.
Configuration for Configuration for Configuration for
2 hours backup time 4 hours backup time 8 hours backup time
EX 5RT 7 hours 15 hours 24 hours
EX 7RT 5 hours 12 hours 20 hours
EX 11RT 7 hours 15 hours 24 hours
Table 5-4: Efficiency online (RL load) and batteries fully charged.
Table 5-5: Efficiency online (RCD load) and batteries fully charged.
Table 5-6: Efficiency on battery (RCD load).
kVA / kW 25% 50% 75% 100% Output load percentage
5kVA /
4kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
89
88
90
90
89
89
87
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
kVA / kW 25% 50% 75% 100% Output load percentage
5kVA /
4kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
90
89
92
91
91
90
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
kVA / kW 25% 50% 75% 100% Output load percentage
5kVA /
4kWatts
90
89
91
90
91
91
91
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
90
89
91
90
91
91
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
90
89
91
90
90
90
90
89
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Appendix 5 — 386-86000-00 B00