Instruction manual
44
15.7.4  Ethernet/IP Port Configuration 
The Ethernet/IP port has the following configuration parameters: 
• Enable/Disable
: Enables or disables this protocol. 
•  Produced/Consumed Assembly Member Lists
: These arrays allow the 
creation of custom-built assembly instances. Each box in the array is 
capable of containing a point number. Because the “value” attributes of 
each point are 16-bit data elements, each box represents two bytes of 
consumed or produced data. 
Up to 100 points can be assigned to each member list (for a total of 200 
bytes of produced and/or consumed data). The array locations are 
numbered 0-99, and traverse from left to right across each row, and then 
increment to the left-most position on the next row. Clicking on a box in an 
array toggles the point that will be referenced when class 1 connected data 
is produced or consumed at that corresponding location. A blank array 
entry indicates that no point is referenced at that location, which will cause 
corresponding consumed data to be ignored and produced data to be a 
default value of 0. 
As an example, looking at the member list definitions shown in Figure 24, 
we can see that each member list contains 6 defined points. Therefore, up 
to 12 “meaningful” bytes of data can be both consumed and produced via 
class 1 connected messages (the qualifier “meaningful” is used here 
because a client may configure a class 1 connection that indicates larger 
produced and/or consumed data sizes, but all unreferenced consumed 
data (data after byte #12) will be ignored, and all unreferenced produced 
data (also data after byte #12) will be dummy “0” values). The first word 
(two bytes) of consumed data will be written to the “value” attribute of point 
#3, the next two bytes to point #4 and so on. If points #3 and #4 etc. have 
a “Source Port” selection defined, then this command data will 
subsequently also propagate to that port and down to the point’s 
configured remote device. 
This example works similarly when describing the behavior of the produced 
member list in Figure 24. In this case, the first 2 bytes of the produced 
data will be the value of point #1, the next two bytes will be the value of 
point #2 and so on. 
15.8  Point Configuration 
The ETH-200 supports 100 total points. The configuration of these points 
determines what data is available from attached network devices. Points are 
configured using the interface shown in Figure 25. 










