Instruction manual
64
•  The MA7200 Modbus manual indicates that control data registers 
(0000H..000FH) are read/write, but reading always returns 0. 
•  All drive parameters may be read at any time, but only Cn parameters can 
be written while the inverter is in DRV mode. The inverter must be in PRG 
mode to write any other parameters. 
•  The drive parameters that configure the RS-485 communication 
characteristics (baud rate, etc.) do not take effect until the drive is reset. 
•  Cn parameter changes take effect instantly, while others don't take effect 
until the inverter is put back into DRV mode or the parameters are saved 
into EEPROM and the inverter is reset. 
•  The “write to EEPROM” register (0900H) is write-only. Therefore, if this 
drive register is mapped to a point in the gateway, this gateway point will 
always be flagged as “in error”, as the gateway will always attempt to read 
this register as long as a new value is not being written to it. The impact of 
this point always being “in error” (if any), is dependant on the protocol used 
to access this point. 
16.6.2  PA7300 
•  Set JP1 on the PA-M card to the "RS-485" position. 
•  Set both SW1-1 and SW1-2 on the PA-M card to the "OFF" position. 
•  Connect the gateway’s RS485 port "A" terminal to the PA-M card’s TB1 "1" 
terminal, the gateway’s RS485 port "B" terminal to the PA-M card’s TB1 "2" 
terminal, and the gateway’s RS485 port "SG" terminal to the PA-M card’s 
TB1 "E" terminal. 
•  Note that the default value of drive parameter Cn-31 (time-out check) is 
1.0s. Because the minimum timeout time that the gateway’s port can be 
configured for is 1s, to avoid nuisance timeout faults on the drive it is 
recommended to either set parameter Cn-31 to 0.0s (if timeout checking is 
not needed), or to a value of 2.0s or more (if timeout checking is desired). 
•  If run/stop etc. commands are to come from network, set Sn-08 to XX0X. 
•  If frequency reference is to come from network, set Sn-08 to XXX0. 
•  When drive parameter Sn-24 is set to XX00 (no parity), the gateway’s port 
configuration must be set to “none / 2 stop bits”. 
•  Note that the holding register “address / HEX” and “address / DEC” 
columns provided in the PA7300 Modbus manual contain the Modbus 
“addressed as” (on-the-wire) values, which are always 1 less than the 
Modbus “known as” values (which the gateway’s configuration requires). 
Therefore, to calculate the “register” assignment that must be programmed 
into the gateway, add 1 to the documented “address / DEC” register 
number. For example, the PA7300’s “output frequency” register is 
documented to exist at decimal register 36. Adding 1 therefore results in a 










