Instruction manual
67
16.7.1  Command Parameters 
Parameter 
Bit Function Bank Mask  Adjustment Range  Multiplier 
0001 word Frequency command 0 FFFF 
0.00 ∼ 400.00Hz 
Actual frequency will be limited by 
LL, UL and Fmax. 
0.01 
0002 0 RUN command  0 
⎯ 
0: Stop 
1: Run 
⎯ 
 1 Reserved    
⎯ 
 2 
Forward • reverse 
run selection 
 0: reverse 
1: forward 
  3  Acc/dec #1 / #2 
selection 
    0: Acc / dec #1 
1: Acc / dec #2 
 4 Reserved    
⎯ 
 5 Reserved    
⎯ 
 6 Reserved    
⎯ 
  7  Jog mode selection      0: Normal (acc/dec mode) 
1: Jog mode 
  8  Feedback control      0: Feedback valid 
1: Feedback invalid 
 9 Compulsory DC 
injection braking 
mode 
    0:  No compulsory DC injection 
braking 
1:  Compulsory DC injection below 
DC INJECTION START 
FREQUENCY 
 A Fundamental 
parameter switching 
    0: V/F #1 
1: V/F #2 
  B  Gate block command 
(coast stop 
command) 
 0: Normal 
1: Gate block 
 C Emergency off 
command 
    0: Does nothing 
1: Emergency off 
 D Reset command 
(trip clear) 
    0: Does nothing 
1: Reset 
 E Reserved    
⎯ 
 F Reserved    
⎯ 
0003  word  RS232 command / 
frequency selection 
0 0003 0000: FREQUENCY MODE 
SELECTION, COMMAND 
MODE SELECTION settings 
0001:  RS232C commands valid 
0002:  RS232C frequency valid 
0003:  RS232C commands and 
frequency valid 
⎯ 
0004  word  Preset speed run 
command 
0  000F  0000:  Output frequency selected 
by FREQUENCY MODE 
SELECTION 
0001 ∼ 000F: speeds 1 ∼ 15 
⎯ 