Instruction manual
69
Parameter Bit  Function  Bank Mask  Adjustment Range  Multiplier 
0012 high 
byte 
2nd past trip  0  7F00   
⎯ 
 low 
byte 
1st past trip (oldest)    007F     
0013 word Pre-compensation output 
frequency 
0 FFFF 
0000 ∼ 9C40 
(0.00 ∼ 400.00 Hz) 
0.01 
0014 word Post-compensation output 
frequency 
0 FFFF 
0000 ∼ 9C40 
(0.00 ∼ 400.00 Hz) 
0.01 
0015  word  Torque current monitor  0  FFFF  (Note 2)  0.01 
0016 low 
byte 
Excitation current monitor  0  00FF 
00 ∼ FF (0 ~ 255%) 
1 
 high 
byte 
Reserved 
⎯  ⎯  ⎯  ⎯ 
0017  word  PID feedback value  0  FFFF  (Note 2)  0.02 
0018  word  Motor overload ratio  0  FFFF  0 ~ 65535  100/65535 
0019 word Inverter overload ratio  0  FFFF  0 ~ 65535  100/65535 
001A  word  DBR overload ratio  0  FFFF  0 ~ 65535  100/65535 
001B  word  Input power (%)  0  FFFF  0 ~ 6553.5  0.1 
001C  word  Input power (kW)  0  FFFF  (Note 3)   
001D  word  Output power (%)  0  FFFF  (Note 2)  0.1 
001E  word  Output power (kW)  0  FFFF  (Note 2, Note 3)   
001F  word  RR input  0  FFFF  0 ~ 65535  100/65535 
0020 
⎯ 
Reserved 
⎯  ⎯  ⎯  ⎯ 
0021 
⎯ 
Reserved 
⎯  ⎯  ⎯  ⎯ 
0022 
⎯ 
Reserved 
⎯  ⎯  ⎯  ⎯ 
0023 low 
byte 
Inverter typeform monitor  0  00FF  Refer to Table 8 (page 
71) 
⎯ 
  8  Input / output power units  0  0100  0: 0.01kW 
1: 0.1kW 
⎯ 
  9,A  Command mode status  0  0600  00: terminal 
01: panel 
10: option 
11: RS232C 
⎯ 
  B,C  Frequency mode selection 
status 
0 1800 00: terminal 
01: panel 
10: option 
11: RS232C 
⎯ 
 D,E,F Reserved 
⎯  ⎯  ⎯  ⎯ 
0024 
⎯ 
Reserved 
⎯  ⎯  ⎯  ⎯ 
0025  word  Output current (amps) 
⎯ 
FFFF  0.0 ~ 6553.5 A  0.1 
(Note 1) .... These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in 
GROUP:UTILITY PARAMETERS; they are always in units of %. 
(Note 2) .... These parameters use signed data (data values larger than 7FFFH are negative). If the parameter data is 
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (parameter data) + 1]. 
(Note 3) .... If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is 0.01. 
If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier is 0.1. 
These values are automatically set according to the inverter’s capacity. 