Instruction manual
72
16.7.3  Fundamental Parameters #1 
Parameter  Function / Title Bank Mask  Adjustment Range  Multiplier 
0026 
MAXIMUM OUTPUT 
FREQUENCY (*) 
0 / 1  FFFF 
0BB8 ∼ 9C40 (30.00∼400.00) 
0.01 
0027 
BASE FREQUENCY #1 
0 / 1  FFFF 
09C4 ∼ 9C40 (25.00∼400.00) 
0.01 
0028 
BASE FREQUENCY 
VOLTAGE SELECT (*) 
0 / 1  0030  0000: Input voltage level  (0) 
0020: Automatic setting  (1) 
0030: Stationary setting  (2) 
⎯ 
0029 
MAXIMUM OUTPUT 
VOLTAGE #1 
0 / 1  FFFF 
0000 ∼ 0258 (0 ∼ 600) 
1 
002A 
REVERSE OPERATION 
DISABLE SELECT 
0 / 1  0020  0000: Reverse allowed  (0) 
0020: Reverse not allowed  (1) 
⎯ 
002B 
UPPER LIMIT FREQUENCY 
0 / 1  FFFF  0000 ~ Fmax  0.01 
002C 
LOWER LIMIT FREQUENCY 
0 / 1  FFFF 
0000 ∼ UL, Fmax 
0.01 
002D 
VOLTS PER HERTZ 
PATTERN (*) 
0 / 1  000F  0000: Constant torque  (1) 
0001: Variable torque  (2) 
0002: Auto. torque boost  (3) 
0006: #3 w/ auto. energy savings (4) 
000A: Vector control  (5) 
000E: #5 w/ auto. energy savings  (6) 
⎯ 
002E 
1, 2 
VOLTAGE BOOST 
#1 
0 / 1  FFFF 
0000 ∼ 012C (0.0 ∼ 30.0) 
0.1 
002F 
ACCELERATION TIME #1 
0 / 1  FFFF 
0001 ∼ EA60 (0.01~ 600.00) 
0001 ∼ EA60 (0.1~ 6000.0) 
0.01 
0.1 
0030 
DECELERATION TIME #1 
0 / 1  FFFF 
0001 ∼ EA60 (0.01~ 600.00) 
0001 ∼ EA60 (0.1~ 6000.0) 
0.01 
0.1 
0031 
ACC/DEC PATTERN #1 
SELECTION 
0 / 1  0030  0000: Linear  (0) 
0010: Self-adjusting  (1) 
0020: S-Pattern #1  (2) 
0030: S-Pattern #2  (3) 
⎯ 
0032 
ACCEL/DECEL PATTERN 
ADJUST LOW 
0 / 1  00FF 
0003 ~ 00FD (0 ∼ 50) (Note 1) 
1 
0033 
ACCEL/DECEL PATTERN 
ADJUST HIGH 
0 / 1  00FF 
0003 ~ 00FD (0 ∼ 50) (Note 1) 
1 
Note 1:  Parameter data = (desired setting x 5 + 3), converted to hexadecimal 