Instruction manual
76
Table 9: Input Terminal Selections 
Setting 
Value 
Data 
(Hex) 
Function 
Setting 
Value 
Data 
(Hex) 
Function 
0  10C8  R  (reverse run)  28  04AF  Binary bit #6 
1  011C  SS1  (preset speed selection)  29  08AF  Binary bit #7 
2  021C  SS2  (preset speed selection)  30  10AF  Binary bit #8 
3  041C  SS3  (preset speed selection)  31  20AF  Binary bit #9 
4  081C  SS4  (preset speed selection)  32  40AF  Binary bit #10 
5  20C8  F  (forward run)  33  04CE  No effect 
6  201B  RES  (fault reset)  34  01C7  UP/DOWN frequency setting (UP) 
7  C0C9  ST  (gate ON/OFF)  35  02C7  UP/DOWN frequency setting 
(DOWN) 
8  0CC8  JOG selection  36  04C7  UP/DOWN frequency clear 
9  081A  Accel / decel #1/#2 selection  37  08C7  PUSH-type RUN key 
10  101B  Emergency off  38  10C7  PUSH-type STOP key 
11  021B  DC injection braking ON/OFF  39  02B9  No effect 
12 041B Fundamental parameter 
switching (V/F #2) 
40  C0C8  Forward/reverse run selection 
13  011B  Feedback control ON/OFF  41  20C7  RUN 
14  10CE  Pattern run selection #1  42  30C9  Binary data write 
15  20CE  Pattern run selection #2  43  0198  [LOCAL/REMOTE] key 
16  40CE  Pattern run selection #3  44  0298  [MON] key 
17  80CE  Pattern run selection #4  45  0498  [PRG] key 
18  02CE  Pattern run continue signal  46  0898  [UP] key 
19  01CE  Pattern run step trigger signal  47  1098  [DOWN] key 
20  0AC9  JOG forward run  48  2098  [READ/WRITE] key 
21  06C9  JOG reverse run  49  4098  [RUN] key 
22  10AE  Binary bit #0  50  8098  [STOP/CLEAR] key 
23  20AE  Binary bit #1  51  08CE  Commercial power / inverter 
switching signal 
24  40AE  Binary bit #2  52  40C7  Reserved for option use 
25  80AE  Binary bit #3  53  10CB  RR frequency switching input 
26  01AF  Binary bit #4  54  20CB  IV frequency switching input 
27  02AF  Binary bit #5       
Note:  In order for binary bit #0 ∼ #10 (setting values 22 ∼ 32) and UP/DOWN frequency setting (setting values 34 & 
35) inputs to be valid, parameter FREQUENCY PRIORITY SELECTION #1 or FREQUENCY PRIORITY 
SELECTION #2 in GROUP:FREQUENCY SETTING PARAMETERS must be set to 5 (BIN (binary setting or 
UP/DOWN setting)). 