Instruction manual
79
16.7.8  Frequency Setting Parameters 
Parameter  Function / Title Bank Mask  Adjustment Range  Multiplier 
0081 
FREQUENCY PRIORITY 
SELECTION #1 
0 / 1  0007  0001: RR  (1) 
0002: IV  (2) 
0003: RX  (3) 
0004: PG  (4) 
0005: BIN  (5) 
⎯ 
0082 
FREQUENCY PRIORITY 
SELECTION #2 
0 / 1  0038  0008: RR  (1) 
0010: IV  (2) 
0018: RX  (3) 
0020: PG  (4) 
0028: BIN  (5) 
⎯ 
0083 
ANALOG INPUT FILTER 
0 / 1  0003  0000: No filter  (0) 
0001: Small filter  (1) 
0002: Medium filter  (2) 
0003: Large filter  (3) 
⎯ 
0084 
RR TERMINAL STANDARD 
OR ADJUSTABLE 
0 / 1  0002  0000: Standard  (0) 
0002: Adjustable  (1) 
⎯ 
0085 
RR REFERENCE 
SETTING POINT #1 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
0086 
RR REF POINT #1 
FREQUENCY 
0 / 1  FFFF 
0000 ∼ Fmax 
0.01 
0087 
RR REFERENCE 
SETTING POINT #2 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
0088 
1 
RR REF POINT #2 
FREQUENCY 
0 / 1  FFFF 
0000 ∼ Fmax 
0.01 
0089 
IV TERMINAL STANDARD 
OR ADJUSTABLE 
0 / 1  0004  0000: Standard  (0) 
0004: Adjustable  (1) 
⎯ 
008A 
IV REFERENCE 
SETTING POINT #1 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
008B 
IV REF POINT #1 
FREQUENCY 
0 / 1  FFFF 
0000 ∼ Fmax 
0.01 
008C 
IV REFERENCE 
SETTING POINT #2 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
008D 
1 
IV REF POINT #2 
FREQUENCY 
0 / 1  FFFF 
0000 ∼ Fmax 
0.01 
008E 
RX TERMINAL STANDARD 
OR ADJUSTABLE 
0 / 1  0008  0000: Standard  (0) 
0008: Adjustable  (1) 
⎯ 
008F 
RX REFERENCE 
SETTING POINT #1 
0 / 1  00FF 
009C ∼ 00FF, 0000 ∼ 0064 
(-100 ∼ -1, 0 ∼ 100) 
1 
0090 
RX REF POINT #1 
FREQUENCY 
0 / 1  FFFF 
-Fmax ∼ Fmax 
0.02 
0091 
RX REFERENCE 
SETTING POINT #2 
0 / 1  00FF 
009C ∼ 00FF, 0000 ∼ 0064 
(-100 ∼ -1, 0 ∼ 100) 
1 
0092 
1 
RX REF POINT #2 
FREQUENCY 
0 / 1  FFFF 
-Fmax ∼ Fmax 
0.02 
0093 
PG TERMINAL STANDARD 
OR ADJUSTABLE 
0 / 1  0010  0000: Standard  (0) 
0010: Adjustable  (1) 
⎯ 
0094 
PG REFERENCE 
SETTING POINT #1 
0 / 1  00FF 
009C ∼ 00FF, 0000 ∼ 0064 
(-100 ∼ -1, 0 ∼ 100) 
1 
0095 
PG REF POINT #1 
FREQUENCY 
0 / 1  FFFF 
-Fmax ∼ Fmax 
0.02 
0096 
PG REFERENCE 
SETTING POINT #2 
0 / 1  00FF 
009C ∼ 00FF, 0000 ∼ 0064 
(-100 ∼ -1, 0 ∼ 100) 
1 
0097 
1 
PG REF POINT #2 
FREQUENCY 
0 / 1  FFFF 
-Fmax ∼ Fmax 
0.02 