Instruction manual
88
16.7.12  Communication Setting Parameters 
Parameter  Function / Title Bank Mask  Adjustment Range  Multiplier 
0204 
INVERTER ID NUMBER 
1 00FF 
0000 ∼ 00FF (0 ∼ 255) 
1 
0205 
COMMUNICATION 
SELECTION 
1 0007 0000: OFF  (0) 
0001: RS485  (1) 
0002: Modbus, F10, DeviceNet (2) 
0003: TOSLINE S-20  (3) 
0004: 12 bit binary input  (4) 
0005: 3-digit BCD (0.1Hz)  (5) 
0006: 3-digit BCD (1Hz)  (6) 
⎯ 
0206 
MASTER/SLAVE 
SELECTION 
1 0018 0000: Slave  (0) 
0008: Master (freq. command)  (1) 
0010: Master (output frequency) (2) 
⎯ 
0207 
1 
RS485 BAUD RATE 
1  0004  0000: Normal mode  (0) 
0004: High-speed mode  (1) 
⎯ 
0208 
TOSLINE-F10 
COMMAND INPUT 
1 0003 0000: OFF  (0) 
0001: Frequency command  (1) 
0002: Command input  (2) 
0003: Both (1) and (2)  (3) 
⎯ 
0209 
TOSLINE-F10 
MONITOR OUTPUT 
1 003C 0000: (0)  0020: (8) 
0004: (1)  0024:  (9) 
0008: (2)  0028:  (10) 
000C: (3)  002C:  (11) 
0010: (4)  0030:  (12) 
0014: (5)  0034:  (13) 
0018: (6)  0038:  (14) 
001C: (7)  003C:  (15 ) 
⎯ 
020A 
2 
TOSLINE-F10 COMM 
ERROR MODE 
1  0080  0000: Data cleared  (0) 
0080: Data retained  (1) 
⎯ 
020B 
TOSLINE-S20 
RECEIVE ADDRESS 
1 FFFF 
0000 ∼ 03FF (0 ∼ 1023) 
1 
020C 
TOSLINE-S20 
TRANSMIT ADDRESS 
1 FFFF 
0000 ∼ 03FF (0 ∼ 1023) 
1 
020D 
TOSLINE-S20 
COMMAND INPUT 
1 001F 
0000 ∼ 001F (0 ∼ 31) 
1 
020E 
TOSLINE-S20 
MONITOR OUTPUT 
1 001F 
0000 ∼ 001F (0 ∼ 31) 
1 
020F 
TOSLINE-S20 FREQ 
REF ADDR SELECT 
1 0001 0000: Disable  (0) 
0001: Enable  (1) 
1 
0210 
1 
TOSLINE-S20 
FREQ REFERENCE 
ADDR 
1 FFFF 
0000 ∼ 03FF (0 ∼ 1023) 
1 
0211 
TOSLINE-S20 COMM 
ERROR MODE 
1  0002  0000: Data cleared  (0) 
0002: Data retained  (1) 
1 
0212 
3 
TOSLINE-S20 COMM 
OPTION RESET 
1  0004  0000: No effect  (0) 
0004: Reset  (1) 
1 
0213 
RS485/12-BIT BINARY 
BIAS,GAIN 
0 / 1  0020  0000: OFF  (0) 
0020: ON  (1) 
⎯ 
0214 
RS485/12-BIT 
BINARY POINT #1 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
0215 
RS485/12-BIT 
BINARY PT. #1 FREQ 
0 / 1  FFFF 
0000 ∼ Fmax (0 ∼ Fmax) 
0.01 
0216 
RS485/12-BIT 
BINARY POINT #2 
0 / 1  00FF 
0000 ∼ 0064 (0 ∼ 100) 
1 
0217 
1 
RS485/12-BIT 
BINARY PT. #2 FREQ 
0 / 1  FFFF 
0000 ∼ Fmax (0 ∼ Fmax) 
0.01 