Instruction manual
Table Of Contents
- SAFETY INSTRUCTIONS
- CONTENTS
- CHAPTER 1 OUTLINE
- CHAPTER 2 INSTALLATION AND WIRING
- CHAPTER 3 OPERATION/CONTROL
- CHAPTER 4 PARAMETERS
- CHAPTER 5 PROTECTIVE FUNCTIONS
- 5.1 Errors (Alarms)
- 5.2 Troubleshooting
- 5.2.1 Motor remains stopped.
- 5.2.2 Motor rotates in opposite direction.
- 5.2.3 Speed greatly differs from the setting.
- 5.2.4 Acceleration/deceleration is not smooth.
- 5.2.5 Motor current is large.
- 5.2.6 Speed does not increase.
- 5.2.7 Speed varies during operation.
- 5.2.8 Operation mode is not changed properly.
- 5.2.9 Operation panel (FR-DU04) display is not provided.
- 5.2.10 POWER lamp is not lit.
- 5.2.11Parameter write cannot be performed
- 5.3 Precautions for Maintenance and Inspection
- CHAPTER 6 SPECIFICATIONS
- CHAPTER 7 OPTIONS
- APPENDICES
- REVISIONS

PARAMETERS
63
z
zz
z Starting frequency (Pr. 13)
Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
z Set the starting frequency at which the start signal is switched on.
Parameter
Number
Factory
Setting
Setting Range
13 0.5Hz 0.01 to 60Hz
<Setting>
60
Pr.13
ON
0
Forward
rotation
Output frequency
(Hz)
Setting range
Frequency setting signal (V)
Time
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
CAUTION
When the Pr. 13 setting is lower than the Pr. 2 value, note that the motor will run at the
set frequency by merely switching the start signal on, without entering the command
frequency.
Pr. 2 "minimum frequency"
Related parameters
4