Instruction manual
Table Of Contents
- SAFETY INSTRUCTIONS
- CONTENTS
- CHAPTER 1 OUTLINE
- CHAPTER 2 INSTALLATION AND WIRING
- CHAPTER 3 OPERATION/CONTROL
- CHAPTER 4 PARAMETERS
- CHAPTER 5 PROTECTIVE FUNCTIONS
- 5.1 Errors (Alarms)
- 5.2 Troubleshooting
- 5.2.1 Motor remains stopped.
- 5.2.2 Motor rotates in opposite direction.
- 5.2.3 Speed greatly differs from the setting.
- 5.2.4 Acceleration/deceleration is not smooth.
- 5.2.5 Motor current is large.
- 5.2.6 Speed does not increase.
- 5.2.7 Speed varies during operation.
- 5.2.8 Operation mode is not changed properly.
- 5.2.9 Operation panel (FR-DU04) display is not provided.
- 5.2.10 POWER lamp is not lit.
- 5.2.11Parameter write cannot be performed
- 5.3 Precautions for Maintenance and Inspection
- CHAPTER 6 SPECIFICATIONS
- CHAPTER 7 OPTIONS
- APPENDICES
- REVISIONS

PARAMETERS
79
z
zz
z Automatic restart after instantaneous power failure (Pr. 57, Pr. 58, Pr. 162 to Pr. 165)
Pr. 57 "coasting time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr. 58 "cushion time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr.162 "Automatic restart after instantaneous power failure selection"
Pr.163 "First cushion time for restart"
Pr.164 "First cushion voltage for restart"
Pr.165 "Restart stall prevention operation level"
z You can restart the inverter without stopping the motor (with the motor coasting) when the commercial
power supply is switched to the inverter operation or when the power is restored after an instantaneous
power failure. (When automatic restart operation is set to be enabled, UVT and IPF among the alarm
output signals will not be output at occurrence of an instantaneous power failure.)
Parameter
Number
Factory
Setting
Setting Range Remarks
57 9999 0, 0.1 to 5 s, 9999 9999: No restart
58 1.0 s 0 to 60 s
162 0 0, 1
0: Frequency search
1: No frequency search
163 0 s 0 to 20 s
164 0% 0 to 100%
165 150% 0 to 200%
(Pr.163)
Pr.58
Pr.164
STF
IM
NFB
CS
SD
CS
SD
S1
R1
T
S
R
MC1
MC2
×
MC3
W
V
U
Connect CS-SD for use of only
automatic restart after instantaneous
power failure.
Voltage
Time
Voltage rise time
MC switching sequence
4