Technical data
ProCon HT 150 / HT 225
2. Installation
2.7
Maximum pipe lengths, Flue gas systems for
ProCon HT 150 / HT 225
Flue gas outlet in a duct, connecting pipe 2 meters with 2x 87° - deflection
Room air dependent operation
mode
ProCon
Connecting pipe
Riser
max. Length [m]
Duct size
HT 150
DN 160
DN 125 rigid
26 m
180 x 180 mm
HT 150
DN 160
DN 125 flexible
17 m
180 x 180 mm
HT 150
DN 160
DN 160 rigid
28 m
220 x 220 mm
HT 225
DN 160
DN 160 rigid
40 m
220 x 220 mm
Air supply from the boiler room
Room air independent operation
mode
ProCon
Connecting pipe
Riser
max. Length [m]
Duct size
HT 150
DN 160
DN 125 rigid
27 m
220 x 220 mm
HT 150
DN 160
DN 160 rigid
40 m
220 x 220 mm
HT 225
DN 160
DN 160 rigid
23 m
220 x 220 mm
HT 225
DN 160
DN 160 rigid
40 m
260 x 260 mm
Air supply:
Air intake can take place via the annular gap of the duct or through the outer wall
.
Max. resistance of the air inlet pipe is 100 PA.
With additional deflections and a more than
2m long connecting pipe, the full installation length reduces
. Each additional elbow reduces
the installation height by
1m respectively. The specifications are standard values and in borderline cases need to be calculated
according to EN 13384-1.
15