Technical data

ProCon
HT
150
/
HT
225
2.
Installation
Use only allowed lubricants to connect flue gas pipes
.
Make sure horizontal components have a
3%
clearance from the boiler
(3
cm
by
1
meter in length),
because condensed water
could otherwise accumulate in the flue gas pipe.
Condensed water in the flue gas pipe may cause operational malfunction.
If the combustion air
/
flue gas outlet
is routed through a ceiling that must have a fire resistance duration,
the panel
through to the panel roof cladding must correspond to the fire rating of the ceiling
.
Legend
for the above flue gas examples
Pos.
Description
Code No.
1
Flue gas pipe with measuring nipple
DN
160,
PPS
96.00060-1785
2
PPS pipe
DN
160x250
mm
PPS pipe
DN
160x500
mm
PPS pipe
DN
160x1000
mm
PPS pipe
DN
160x2000
mm
96.00060-0740
96.00060-1705
96.00060-1710
96.00060-1720
3
PPS revised pipe
DN
160
96.00060-1770
10
Inlet air screen
11
Fixed vent screen,
rigid
DN
160,
Stainless steel
96.00060-1702
12
Chimney support
DN
160,
87°,
PPS
96.00060-1796
13
Spacer
DN
160,
total
2
m
96.00060-1713
14
Fixed chimney
head cover,
rigid,
DN
160,
Stainless steel
96.00060-1711
15
Flap valve
21
PPS pipe
DN
125x250
mm
PPS pipe
DN
125x500
mm
PPS pipe
DN
125x1000
mm
PPS pipe
DN
125x2000
mm
96.00060-0690
96.00060-1205
96.00060-1210
96.00060-1220
22
PPS pipe
DN
125x500
mm
with
measuring nipple
96.00060-0691
23
PPS revised pipe
DN
125
96.00060-1270
Table
5:
23