Technical data

ProCon
HT
150
/
HT
225
2.
Installation
Outdoor temperature sensor
Connect the outdoor sensor with a two-core cable
(interchangeable
) to the
ATS terminal
.
See table below for cable
profile:
Bus clip-in
OCI
420
The
bus module makes it possible for the boiler control
system to communicate with RVA
series external control
devices
Table
6:
For resistance value
s see diagrams in Chap
7.3
BUS
The
L
o
c
a
l
Proc
ess
Bus
(LPB)
is used as the communication
base for
setting up a system with additional MHG heating
circuit controllers or external controllers.
The terminal is open if the input is not in use.
The functions of the
L
P
B
are described in detail in the
MBW
RVA
47.320 instruction manual
included in the scope of delivery
The maximum wire length of a double wire circuit for the bus
is 100m.
DW
pump
Connects to an
ex
ternal d
omestic water charge pump
.
The boiler is
equipped
with an internal
water deflector
.
HC
Pump
Connects to an external heating circuit pump.
The boiler is
equipped with an internal water deflector.
Mains connection
Connection to the mains is carried out on the terminal block with a
3
x
1.5
mm
2
cable cross-section.
Make sure that ground and phase are not mixed up
If an under floor heater runs
directly with the boiler,
then the recommended safety temperature limiter of
the under floor heater should be looped into the
mains lead of the under floor heating circuit/
circulation pump boiler
.
Fig
14:
Installation of bus
clip-in
The
Bus clip-in
is snapped directly unto the boiler control
system and connected to the boiler control with a five-core
ribbon cable
(Terminal
X40).
(See
pictures below).
There is a 2-pin plug available for connecting to the
L
P
B bus
25
Length
[m]
Minimum section
[mm²]
Up
to18
0.125
18…35
0.25
35…50
0.5