Technical data

ProCon
HT
150
/
HT
225
3.
Start-up
3.1
Operating ProCon
HT
150
/
HT
225
3.2
Setting boiler and room set point value
ProCon
HT
150
carries
two
75
kW
heat generator modules as
well as a
cascade and a heating circuit controller
(RVA
47).
Each
h
eat generator module has a module control unit (
L
MU).
The
L
M
U
controls
and regulates the heat generator module.
ProCon
HT
225
carries three
75
kW
heat generator m
odules
as
well as a cascade a
nd
a
heating circuit controller
(RVA
47).
Each of
the three h
eat generator modules
has a module control unit
(L
MU).
The
L
M
U
controls and regulates the h
eat generator module.
By means of the
corresponding c
ontrol unit
(AGU)
each
L
M
U
can be manually switched on or switched to control stop for the
purpose of adjustment
.
Con
HT
150
/
HT
225
control panel houses the c
ascade
control,
three
AGU's,
the main switch,
the fuse and a
pressure
gage
.
Fig
15:
Control panel
RVA
47
assumes the cascade function,
weather
control,
the
heating program and the d
omestic water program. The functions of
the controller are described in detail in
MBW
RVA
47.320
instruction manual included in the scope of delivery.
The
boiler and r
oom set point value functions are described in detail
in the installation/operation/maintenance
RVA
47.320 instruction
manual included in the scope of delivery.
3.3
Setting domestic water temperature
The domestic water temperature
function is described in detail in
MBW
RVA
47.320 instruction manual
included in the scope of
delivery
.
3.4
Programming ProCon
HT
150
/
HT
225
All
the parameters associated with the heating system should be
set in the
RVA
.
The functions of the controller are described in
detail in
MBW
RVA
47.320 instruction manual included in the
scope of delivery
.
The
L
M
U
can only be programmed by means of an optional
QAA
73 indoor unit.
Programming of the
L
M
U
is only necessary if you
need to replace an original component
.
Unused heating circuits must be switched off in
p
a
ra
me
te
r
17
(Heating characteristics
)
.
Otherwise
heat will be
provided for nonexistent heating circuits.
LPB bus
Allocation of device and segment addresses:
The
L
P
B bus
organizes the connection of
several heat generators
and heating circuit controller
s by allocating distinct addresses to the
c
ascade and heating circuit controller
RVA
47,
the module control
unit
L
M
U
as well as the
heating circuit controllers.
An expert
allocates the addresses during start-up.
Two parameters (Device
address
140
and
segment address
141)
are available for this
purpose
.
The allocation is carried out according to the following
rules:
1.
The controllers of the heat generator
receive s
egment address
0.
The controllers of the heating circuits receive segment address
1.
The address format consists of two
points
for the s
egment
address and two points for the device address separated by a
period e.g.
RVA
47
with the address
00.01
2.
D
RVA
47
always receives the Device address
1.
RVA
47
can address up to
12
L
M
U's.
The
L
M
U
of the heat generator module
receives the Device
addresses
2
upwards irrespective of whether it is the master
or slave cascade boiler
.
3.
Never allocate an address twice
.
27