Technical data

3.
Start-up
ProCon
HT
150
/
HT
225
3.5
Starting up
ProCon
HT
150
/
HT
225
Before starting up, read the instruction manual carefully
and makes sure that
:
-
The gas pipe is adequately vented. If inadequately
vented, heavy
CO2
fluctuations will occur in the first
minutes of operation.
.
-
The tank is well vented in the case of liquid gas equipment
!
-
The gas pipe is tested for tightness
!
Test the gas inlet pipe under pressure only up to the
gate valve.
Note that the compact gas fitting cannot
withstand the high test pressure.
-
The heating system and if possible the storage tank are filled
and vented.
-
The electrical connection was properly carried out.
-
The hydraulics of the appliance is properly connected
-
The condensate trap
(siphon)
is adequately filled.
Check once again to make sure all necessary safety devices
are properly installed.
Then fill the appliance and the heating system.
Filling process
To determine the correct filling pressure, follow the manufacturer specifications of the
p
ressure expansion tank.
We recommend
that you proceed
according to
MHG information on
“Sizing of pressure expansion
tanks”. A filling pressure of 0.5 to 0.8 bars above the inlet
pressure
of the
pressure expansion tank
is sufficient
.
To vent the
boiler, open the hand vent on the h
eat exchanger
and let the air
escape into a pail through the enclosed plastic hose.
Do not end filling until
ProCon
and the heating system
have been completely vented
.
Add anticorrosive
INIBAL
Plus
(
1-2
kg
to
100
l
water to
the heating circuit water, (
see also
Certificate of Warranty).
Filling the siphon
To fill the siphons,
pull out the
condensate hose
from the heat
exchanger and carefully pour water into the s
iphon
(approx
.
¾
l)
until the water flows out of the condensate
outlet
.
Inspecting the pumps
-
Inspect the circulation pumps
-
After unscrewing the pump plugs, turn the pump shaft
(see picture
below
)
-
Screw in the pump plug once again
-
Caution
:
Collect drips
Fig
16:
Release the pump plugs
Switching on and starting
-
Open all
ball valves
as well as the
gas valve
-
Turn on device at the
I/O switch
-
Change control with the button
from
standby
to
continuous operation
.
Setting the compact gas fitting
Fig
17:
Kromschröder
CG
10 compact gas fitting
N
=
Adjusting screw
Min. capacity
D
=
Adjusting screw
Max. capacity
A
=
Measuring nipple
input pressure
B
=
Measuring nipple
nozzle pressure
Use 2.5
mm hexagon key for all settings
Do not
apply force
!
28