Technical data
ProCon
HT
150
/
HT
225
7.
Technical documentation
Line
Level
Func
tion
Range
Valu
e
536
Specialist
Max.
speed
at
max.
capacity in heating operation
(upper
speed limit)
0
...
9950
rpm
7000
rpm
541
Specialist
Maximum
modulation level in heating operation
(LmodTL
<=
PhzMax
<=
LmodVL)
0
...
100
%
100%
542
3)
Specialist
Min.
boiler capacity
in
kW
0
...
32766
kW
15
kW
543
3)
Specialist
Max.
boiler capacity
in
kW
0
...
32766
kW
75
kW
544
Specialist
Pump - overrun time,
max
.
210
minutes
(Setting
255:
Continuous operation of
Q1)
0
...
255
min
10
min
545
Specialist
Minimum idle time of boiler
(heating demand controlled
switch hysteresis)
0
...
3600
s
300
s
551
Specialist
Constants for rapid reduction without ambient effect
0
...
20
2
552
Specialist
Hydraulic system adjustment
0
...
255
80
Specialist
Adjustment flags:
Message code
Sensor interruption suppressed
/not suppressed
,
0
=
Error
message
suppressed
,
1
=
Error message
0
...
255
0
0
1
0
1
1
0
1
B
0
Return sensor
0
/
1
1
B
1
Domestic water sensor
0
/
1
0
B
2
Flue gas sensor
0
/
1
1
B
3
Outdoor sensor
0
/
1
1
B
4
Hydraulic
pressure sensor
0
/
1
0
B
5
Flow sensor
0
/
1
1
B
6
Empty
---
0
554
B
7
Empty
---
0
Specialist
Adjustment flags
0
...
255
0
0
0
1
0
0
0
0
B
0
Empty
0
0
B
1
Domestic water priority
,
0
=
absolute,
1
=
no priority
0
/
1
0
B
2
Function unused
0
0
B
3
Function unused
0
0
B
4
System frost protection
,
0
=
Off,
1
=
On
0
/
1
1
B
5
Function unused
0
0
B
6
Empty
---
0
555
B
7
Empty
---
0
Specialist
Adjustment flags
0
...
255
0
1
0
0
0
0
0
1
B
0
Must be on
1
0
/
1
1
B
1
Building construction
0
=
simple
,
1
=
complex
0
/
1
1
B
2
Domestic water thermostat
0
/
1
0
B
3
Empty
---
0
B
4
Empty
---
0
558
b
5...7
3-way valve
domestic water
010
=
On
XXX
010
596
Specialist
Runtime of mixer drive
(Time on
/
Time off)
30
...
873
s
150
s
605
Specialist
LPB
device number of
LMU
0
...
255
2,
3,
4
606
Specialist
LPB
segment number
of
LMU
0
...
14
0
614
Specialist
Program.
input
(0:
Deerror,
1:
Modem funct.,
2:
Modem funct. neg.logic,
3:
Curtain)
0
...
255
3
615
Specialist
Programmable output
K2
(0:
Deerror
,
1:
Message displayed.,
2:
Alarm signal
3:
Operation message,
4:
ex
t.
Transf.,
5:
Q2Y2
,
6:
DW circ..,
7:
Curtain,
8:
Hydr.
switch,
9:
RegCI,
10:
Basic funct.-K2,
11:
DW Loading Through
(Dur
c
hldg),
12:
Analogue threshold
)
0
...
255
0
618
Specialist
Progr.
Input on relay clip-in.
(0:
Deerror,
1:
Modem funct.,
2:
Modem funct.
neg. l
ogic,
3:
Curtain
,
4:
Target s
et point value spec.,
5:
Target capacity
,
6:
sensor
hy
dr.
switch
)
0
...
255
0
57