Technical data

ProCon
HT
150
/
HT
225
7.
Technical documentation
Parameter
536
Setting the maximum heating capacity
It specifies the speed for the max. heating capacity of a heat
generator module and enables the reduction of the max.
module capacity.
Parameter
541
Setting the max.
heating capacity
It specifies the
PW
M
signal
in
percentage for the m
aximum
heating
capacity
of the heat generator module and enables the reduction of the
module capacity. The max. speed attained should be entered into
parameter
536.
You can read off the speed in the display level of
control unit
C2
(see Chap 7.5)
Parameter
552
Hydraulic systems
It is used for adjusting the module control. This parameter
value must be at 80.
Parameter
605
Setting of the device address
(Cascade)
The
device address
and
the segment address
are a type of address
in the bus system.
Each device must be correctly addressed in order to
ensure smooth communication with the connected module controls
L
M
U
as well as the cascade and heating circuit control
RVA
47
.
The device address
should be assigned
continuously with the
conne
cted devices. Do not assign an address multiple times in a
bus segment because it will cause communication errors.
Each
segment must have a master device
(Address 1).
Parameter
606
Segment address
ProCon
HT
is a system
made up of several control units
(LMU,
RVA
47).
This system is the heat generator se
gment
and can be
constructed from a single
ProCon
HT
or several
ProCon
HTs
connected in cascade
.
The heat generator s
egment
has s
egment
address
0.
This means that all control units
in the heat generator
segment in parameter 606 for LMU and in parameter 141 for
RVA 47 have the value 0.
The heating circuit controls
(e.g.
RVA
63,
RVA
46)
in complex
heating systems constitute a segment made up of heat
consumers.
You can assign the segment addresses1 to 14 to
these segments.
It is better to combine several h
eating circuits of a
building into one segment.
Different segments are only
necessary in the case of several buildings. All controls in a
segment must have the same segment address
.
You can define a
maximum of 14 segments
(The standard setting is
0).
Parameter
630
Resetting maintenance request
with
QAA
73
You can rest the m
aintenance request
in queue
in
the
control
unit with the
QAA
73
by setting the
Bit
6
(Parame
ter
630)
b6
from
0
to
1.
The maintenance meter restarts afresh and displays the
maintenance request anew after one year
.
(
Warning
!
Do not
adjust the b
its
.
)
Address
Effect
Example
0
Single operation
Not active
1
Cascades and heating
circuit control
(Master)
RVA
47
2...16
Module control
or
heating circuit
co
ntrol
(Slave)
L
M
U, RVA
63,
RVA
46
Table
12:
59