Technical data

ProCon
HT
150
/
HT
225
7.
Technical documentation
7.10
Technical data
ProCon
HT
150
/
HT
225
Typ
e
ProCon
HT
150
H
ProCon
HT
225
H
Product ID number
CE
-
CE
-
Category
II2ELL3/P
II2ELL3/P
Volume of hot water in boiler
l
30
35
Boiler weight
kg
250
270
Measurements
(L x B x H
)
mm
1650
x
680
x
1030
Hot water connections
F
l
ange
DIN
2631
DN
40
/
48.3
PN
6
Gas connection
R
Flue gas connection
DN
160
Inlet air connection
DB
125
Inlet air/flue gas-connecting pieces
DN
160
Condensed water run-up
Hose spout
D
=
20
mm
Condensed water drain
DN
20,
¾
AG,
flat sealing
Rated thermal load
kW
15.0
149.2
15.0
216.0
Rated thermal load
80/60°C
kW
14.5
143.2
14.5
206.0
Rated thermal load
50/30°C
kW
16.0
155.0
16.0
225.0
Degree of efficiency
40/30°C
%
109.5
Ga
s types
Natural gas
E
/
LL
Liquid gas
Natural gas
E
/LL
Liquid gas
Nozzle-
mm
15.0
10.0
15.0
10.0
CO
2
content
Vol.%
9.0
11.0
9.0
11.0
Flue gas temperature
80/60
°C
74
Flue gas mass flow rate
kg
/s
0.0697
0.0643
0.1010
0.0931
Manometer
pressure on the f
lue gas connecting
pieces
Pa
200
200
200
200
Permissible
flue gas lead
B
23
,
C
33
,
C
43
,
C
53
,
C
63
,
C
83
pH value of c
ondensed water
4...5.5
Gas connection pressure
Natural gas
E
/
LL
Liquid gas
Natural gas E
L
Liquid gas
Min.
mbar
18.0
30.0
18.0
30,0
Max
.
mbar
30.0
50.0
30.0
50.0
Maximum
gas
connection pressure,
P
imax
mbar
70
Electrical connection
V/Hz
230
/
50
Max
.
electr.
power consumption
W
690
800
Max
.
operating pressure
bar
3.0
Min.
system pressure
bar
0.5
Switching on
threshold
hydraulic pressure switch
bar
0.8
Flow rate at
∆ϑ
=
20°C
l/h
6500
9600
Max.
flow temperature
°C
90°
63