"MOJO" Series Unvented Gas Log Sets
To install the heater with a wooden mantel, shelf or other
combustible projection above, first measure the heat resis-
tant material shown in then refer to Table B.
12” or more Hood not required. Observe profile
(side elevations) shown in
8” or less than 12” Install hood and observe profiles in
; extend heat resistant mate-
rial to at least 12" and observe profiles in
.
Less than 8" Extend heat resistant material to at
least 8", install hood and observe pro-
files in ; extend heat resis-
tant material to at least 12" and observe
profiles in.
FP1998
heat resist mantel
Hood
Heater in
Fireplace or
Firebox
8" or More of
Heat Resistant
Materials
FP1998
Figure 6 -
Measuring Heat Resistant Material for Mantel
TABLE B -
Heat Resistant Material Heights and Mantel Location
Figure 7 -
Minimum Mantel Clearance with Hood - All Models
10"
12"
8"
6"
2
1
/2
"
8" 14
1
/2
"18
5
/8
" 22
1
/2
" 26"
FP1999
min. mantel clearance
Heat
Resistant
Material
Hood
Heater in
Fireplace or
Firebox
FP1999
Example: A mantel may
project from the wall a
of 2Z\x" at a
of 8" above the opening,
and a maximum of 6" at a
of 14Z\x" above
the opening.
Figure 8 -
Minimum Mantel Clearance with No Hood — MJ27
Example: The bottom of
the mantel may project
from the wall a maximum
of 10" at a minimum of 28"
above the opening.
12" min. 28"
FP2001
minimum mantel clearance no hood
Heat Resistant
Material
Heater in Fireplace
or Firebox
FP2001
10" or Less