Hydromatic II Chiller Operation Manual

Table Of Contents
Page 11
Rev 1.07 ©2015 Micro Air Corp 10/26/2015
Freon sensor type
Sets the type of sensor connected to the high and low Freon pressure input. If only a
switch is installed, the parameter is set for switch and JP12 and JP 13 must have jumpers
installed.
If the parameter is set for gauge or both, JP12 and JP 13 jumpers must be removed. The
following options will also become available:
Hi. Pressure maximum PSI
Hi. Pressure 0 PSI voltage
Low pressure maximum PSI
Low pressure 0 PSI voltage
This system is compatible with standard pressure sensors operating in the 0 to 5 VDC
range. These options allow independent setting of the pressure sensor connected. Set the
maximum PSI parameter to the maximum pressure the sensor measures. Set the 0 PSI
voltage to the 0 PSI reference voltage specified by the sensor manufacturer.
Water Sensor Type
Sets the type of sensor connected to the water pump LPS and HPS terminals.
The following options will become available if “Gauge” or “Both” are selected:
LPS Pressure maximum PSI
LPS Pressure 0 PSI voltage
HPS pressure maximum PSI
HPS pressure 0 PSI voltage
This system is compatible with standard pressure sensors operating in the 0 to 5 VDC
range. These options allow independent setting of the pressure sensor connected. Set the
0 PSI voltage to the 0 PSI reference voltage specified by the sensor manufacturer. Set the
maximum PSI parameter to the pressure the sensor measures at 4 volts above the 0 PSI
reference voltage. This will typically be the maximum PSI reading for the sensor used.
System units
Sets the system units for metric (°C) or US standard (°F)
Pump Station Delay
Sets the minimum length of time needed to respond to an open flow switch on the pump
relay board.
Reset parameters
Reset parameters to factory default values. (If Reset Parameters is used on any unit it
should be repeated on all other units in system. The system should then be set up from the
beginning. See the initial configuration section for details.)