Hydromatic II Chiller Operation Manual

Table Of Contents
Page 24
Rev 1.07 ©2015 Micro Air Corp 10/26/2015
Specifications
Set point range:
Cooling 35°F to 57°F
1.7°C to 13.9°C
Heating 100°F to 140°F
37.8°C to 60°C
Temperature range displayed 5°F to 150°F
Sensor accuracy +/-2°F at 77°F
Low voltage limit 115 VAC units 75VAC
Low voltage limit 230 VAC units 175VAC
Line high voltage limit 250VAC
Frequency 50 or 60 Hz
Heater output MAX .5 Amps AC
Valve output MAX .5 Amps AC
Pump output MAX .5 Amps AC
Compressor output MAX .5 Amps AC
Minimum operating temperature 0°F
Maximum operating temperature 180°F
Maximum RH conditions 95% Non-condensing
Maximum length for sensor cables 50 Feet (15 meters)
Maximum CAN system cable length 750 Feet (228 meters)
Flow and pressure switches normally closed.
Current transformer Future Option
VFD dry contact output 28 VAC Maximum
40 VDC Maximum
100 mA Maximum